Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2013-07-23 — NY
Operator
Consolidated Edison Co Of New York
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$69,000
Incident datetime
2013-07-23 01:46
Report number
Location
NY, WESTCHESTER
Narrative
On july 23,2013 at 01:46 westchester fire control reported a building fire with a gas odor at this location to the gas emergency response center (gerc). Gas distribution services (gds) and supervision were dispatched. At 02:02 westchester fire control called a second time and reported a gas ignition at the same location (still believed to be a building fire). Gds was updated and arrived at 02:14. The gerc provided gds measurements to locate a 4" 1956 medium pressure (mp) main valve-27428 which would have isolated the incident affecting 9 residential services. Gds was unable to locate the main valve and 4 backup main valves were identified and provided by gerc. Gas emergency response force (erf) excavated the location of mv-27428 and was unable to locate. The (4) main valves on the mp distribution system were located by gds and closed by 04:03. The flame decreased in size but did not extinguish. System pressures in the area and were monitored in response to closure of a 8" mp mv-30551 at gas regulator-583 and were adequate. Westchester erf and bronx erf excavated to locate primary shutoff valve mv-27428. Two residents from 1605 and two residents from 1611 winfield ave were evacuated by mamaroneck fd (mmfd) as a precaution. At 06:36 primary valve mv-27428 was exposed and closed extinguishing the fire and securing the leak. This valve was discovered under a water department valve box cover and "rite height" valve box extension due to the area recently being paved. This condition concealed the gas valve box cover correctly installed over mv-27428. Nine confirmed outages on winfield ave. Only was the extent of the customer impact. Three visible holes approximately the size of a half dollar each were discovered in the mp gas main located directly under the pavement where the "a" phase burned three holes in the pavement. The "a" phase of 13 kv bowman auto-loop is suspected to be the cause of the fire. The customer in 1605 winfield ave reported lights were flickering inside his home, he saw sparks and then saw an overhead wire fall and then heard a booming sound. Mmfd reported 2-3 private vehicles (>$50,000 damage) were on fire then realized natural gas was involved, per news 4 tv reporting. No injuries reported or structures impacted. The evacuation of 1605 and 1611 winfield avenue was terminated at 07:05. No gas odor or readings were detected in any sub surface structures (sss) or buildings. Channel 4 & channel 2 tv news were on location and photographic and law depts. Responded. The US DOT, nys psc, emergency management, media relations and public affairs were notified. Mmfd chief pecchia was on location. The psc called,was updated and responded to location. Gas construction worked around the clock and inserted the 4" mp steel main with 3" mp polyethylene. At 10:51 the serious level incident status was terminated. On july 24, 2013 at 12:51 gds completed restoration to the last customer impacted.
Detailed record list
Occurred At
2013-07-23 01:46:00
Year
2013
Report Received Date
2013-08-14 00:00:00
Iyear
2013.0
Report Number
20130090.0
Supplemental Number
15887.0
Report Type
Supplemental Final
Operator Id
2704
Name
Consolidated Edison Co Of New York
Operator Street Address
4 Irving Place
Operator City Name
New York
Operator State Abbreviation
NY
Operator Postal Code
10003
Local Datetime
2013-07-23 01:46:00
Location Street Address
1605 Winfield Ave
Location City Name
Village Of Mamaroneck
Location County Name
Westchester
Location State Abbreviation
NY
Location Postal Code
10543
Location Latitude
40.967746
Location Longitude
-73.736322
Nrc Rpt Datetime
2013-07-23 04:23:00
Nrc Rpt Num
1054756
Commodity Released Type
Natural Gas
Unintentional Release
57.5
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
4.0
Incident Identified Datetime
2013-07-23 01:46:00
On Site Datetime
2013-07-23 02:14:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
60.0
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Main
Installation Year
1955.0
Pipe Diameter
4.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Release Type
Leak
Leak Type
Pinhole
Leak Type Other
Electric Arcing
Class Location Type
Class 4 Location
Est Cost Oper Paid
55000.0
Est Cost Prop Damage
69000.0
Est Cost Emergency
11638.0
Est Cost Other
500.0
Est Cost Other Details
Materials
Est Cost Unintentional Release
115.0
Prpty
136253.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
9.0
Accident Psig
11.0
Normal Psig
11.0
Mop Psig
15.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Electrical Arcing From Other Equipment Or Facility
Outside Force Type
Electrical Arcing From Other Equipment Or Facility
Preparer Name
K**** F****
Preparer Title
Operations Manager-Gas Emergency Response Center
Preparer Email
F*****@c****.com
Preparer Telephone
718-319-2340
Preparer Fax
718-904-4607
Authorizer Name
V***** D******
Authorizer Title
Department Manager-Gas Emergency Response Center
Authorizer Telephone
718-319-2350
Authorizer Email
D*******@c****.com
Narrative
On july 23,2013 at 01:46 westchester fire control reported a building fire with a gas odor at this location to the gas emergency response center (gerc). Gas distribution services (gds) and supervision were dispatched. At 02:02 westchester fire control called a second time and reported a gas ignition at the same location (still believed to be a building fire). Gds was updated and arrived at 02:14. The gerc provided gds measurements to locate a 4" 1956 medium pressure (mp) main valve-27428 which would have isolated the incident affecting 9 residential services. Gds was unable to locate the main valve and 4 backup main valves were identified and provided by gerc. Gas emergency response force (erf) excavated the location of mv-27428 and was unable to locate. The (4) main valves on the mp distribution system were located by gds and closed by 04:03. The flame decreased in size but did not extinguish. System pressures in the area and were monitored in response to closure of a 8" mp mv-30551 at gas regulator-583 and were adequate. Westchester erf and bronx erf excavated to locate primary shutoff valve mv-27428. Two residents from 1605 and two residents from 1611 winfield ave were evacuated by mamaroneck fd (mmfd) as a precaution. At 06:36 primary valve mv-27428 was exposed and closed extinguishing the fire and securing the leak. This valve was discovered under a water department valve box cover and "rite height" valve box extension due to the area recently being paved. This condition concealed the gas valve box cover correctly installed over mv-27428. Nine confirmed outages on winfield ave. Only was the extent of the customer impact. Three visible holes approximately the size of a half dollar each were discovered in the mp gas main located directly under the pavement where the "a" phase burned three holes in the pavement. The "a" phase of 13 kv bowman auto-loop is suspected to be the cause of the fire. The customer in 1605 winfield ave reported lights were flickering inside his home, he saw sparks and then saw an overhead wire fall and then heard a booming sound. Mmfd reported 2-3 private vehicles (>$50,000 damage) were on fire then realized natural gas was involved, per news 4 tv reporting. No injuries reported or structures impacted. The evacuation of 1605 and 1611 winfield avenue was terminated at 07:05. No gas odor or readings were detected in any sub surface structures (sss) or buildings. Channel 4 & channel 2 tv news were on location and photographic and law depts. Responded. The US DOT, nys psc, emergency management, media relations and public affairs were notified. Mmfd chief pecchia was on location. The psc called,was updated and responded to location. Gas construction worked around the clock and inserted the 4" mp steel main with 3" mp polyethylene. At 10:51 the serious level incident status was terminated. On july 24, 2013 at 12:51 gds completed restoration to the last customer impacted.
| Occurred At | 2013-07-23 01:46:00 |
|---|---|
| Year | 2013 |
| Report Received Date | 2013-08-14 00:00:00 |
| Iyear | 2013.0 |
| Report Number | 20130090.0 |
| Supplemental Number | 15887.0 |
| Report Type | Supplemental Final |
| Operator Id | 2704 PHMSA Enforcement |
| Name | Consolidated Edison Co Of New York |
| Operator Street Address | 4 Irving Place |
| Operator City Name | New York |
| Operator State Abbreviation | NY |
| Operator Postal Code | 10003 |
| Local Datetime | 2013-07-23 01:46:00 |
| Location Street Address | 1605 Winfield Ave |
| Location City Name | Village Of Mamaroneck |
| Location County Name | Westchester |
| Location State Abbreviation | NY |
| Location Postal Code | 10543 |
| Location Latitude | 40.967746 Google Maps OpenStreetMap |
| Location Longitude | -73.736322 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2013-07-23 04:23:00 |
| Nrc Rpt Num | 1054756 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 57.5 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Explode Ind | No |
| Num Pub Evacuated | 4.0 |
| Incident Identified Datetime | 2013-07-23 01:46:00 |
| On Site Datetime | 2013-07-23 02:14:00 |
| Federal | No |
| Location Type | Public Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Pavement |
| Depth Of Cover | 60.0 |
| Crossing | No |
| Pipe Facility Type | Privately Owned |
| System Part Involved | Main |
| Installation Year | 1955.0 |
| Pipe Diameter | 4.0 |
| Pipe Specification | Unknown |
| Pipe Manufacturer | Unknown |
| Material Involved | Steel |
| Steel Seam Type | Other |
| Steel Seam Type Details | Unknown |
| Release Type | Leak |
| Leak Type | Pinhole |
| Leak Type Other | Electric Arcing |
| Class Location Type | Class 4 Location |
| Est Cost Oper Paid | 55000.0 |
| Est Cost Prop Damage | 69000.0 |
| Est Cost Emergency | 11638.0 |
| Est Cost Other | 500.0 |
| Est Cost Other Details | Materials |
| Est Cost Unintentional Release | 115.0 |
| Prpty | 136253.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 9.0 |
| Accident Psig | 11.0 |
| Normal Psig | 11.0 |
| Mop Psig | 15.0 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Emergency Responder |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Other Outside Force Damage |
| Cause Details | Electrical Arcing From Other Equipment Or Facility |
| Outside Force Type | Electrical Arcing From Other Equipment Or Facility |
| Preparer Name | K**** F**** |
| Preparer Title | Operations Manager-Gas Emergency Response Center |
| Preparer Email | F*****@c****.com |
| Preparer Telephone | 718-319-2340 |
| Preparer Fax | 718-904-4607 |
| Authorizer Name | V***** D****** |
| Authorizer Title | Department Manager-Gas Emergency Response Center |
| Authorizer Telephone | 718-319-2350 |
| Authorizer Email | D*******@c****.com |
| Narrative | On july 23,2013 at 01:46 westchester fire control reported a building fire with a gas odor at this location to the gas emergency response center (gerc). Gas distribution services (gds) and supervision were dispatched. At 02:02 westchester fire control called a second time and reported a gas ignition at the same location (still believed to be a building fire). Gds was updated and arrived at 02:14. The gerc provided gds measurements to locate a 4" 1956 medium pressure (mp) main valve-27428 which would have isolated the incident affecting 9 residential services. Gds was unable to locate the main valve and 4 backup main valves were identified and provided by gerc. Gas emergency response force (erf) excavated the location of mv-27428 and was unable to locate. The (4) main valves on the mp distribution system were located by gds and closed by 04:03. The flame decreased in size but did not extinguish. System pressures in the area and were monitored in response to closure of a 8" mp mv-30551 at gas regulator-583 and were adequate. Westchester erf and bronx erf excavated to locate primary shutoff valve mv-27428. Two residents from 1605 and two residents from 1611 winfield ave were evacuated by mamaroneck fd (mmfd) as a precaution. At 06:36 primary valve mv-27428 was exposed and closed extinguishing the fire and securing the leak. This valve was discovered under a water department valve box cover and "rite height" valve box extension due to the area recently being paved. This condition concealed the gas valve box cover correctly installed over mv-27428. Nine confirmed outages on winfield ave. Only was the extent of the customer impact. Three visible holes approximately the size of a half dollar each were discovered in the mp gas main located directly under the pavement where the "a" phase burned three holes in the pavement. The "a" phase of 13 kv bowman auto-loop is suspected to be the cause of the fire. The customer in 1605 winfield ave reported lights were flickering inside his home, he saw sparks and then saw an overhead wire fall and then heard a booming sound. Mmfd reported 2-3 private vehicles (>$50,000 damage) were on fire then realized natural gas was involved, per news 4 tv reporting. No injuries reported or structures impacted. The evacuation of 1605 and 1611 winfield avenue was terminated at 07:05. No gas odor or readings were detected in any sub surface structures (sss) or buildings. Channel 4 & channel 2 tv news were on location and photographic and law depts. Responded. The US DOT, nys psc, emergency management, media relations and public affairs were notified. Mmfd chief pecchia was on location. The psc called,was updated and responded to location. Gas construction worked around the clock and inserted the 4" mp steel main with 3" mp polyethylene. At 10:51 the serious level incident status was terminated. On july 24, 2013 at 12:51 gds completed restoration to the last customer impacted. |