GD incident on 2013-06-04 — NY

Operator
Orange & Rockland Utility Inc
Cause
Excavation Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 8 injuries
Property damage (nominal)
$0
Incident datetime
2013-06-04 11:55
Report number
Location
NY, ROCKLAND
Narrative
Nyack college is a campus comprised of multiple buildings. Orange & rockland utilities provides natural gas and electric services to a number of the buildings including 177 south highland avenue known as sky island lodge and 154 south highland avenue known as bowman gymnasium. On tuesday, june 4, 2013 at approxiamately 1155 the gas emergency response center (gerc) received a call from rockland county fire control of a gas explosion at the sky island lodge. Gerc immediately dispatched all available units. The first two responders arrived at 1205 and 1206 respectively. A strong odor of gas was present in the air and gas vapors could be seen coming from the sewer clean out located along the curbline of 177 south highland avenue, the sky island lodge. The o&r servicemen immediately began a leak investigation. High concentrations of gas were detected in the outdoor sewer clean-outs, catch basin and sewer manhole. There were no gas readings in the test points taken in the earth. Covers on the sewer clean outs and manholes were removed allowing these structures to vent. At 1211, a 7% gas-in-air reading was recorded in atmoshere inside the damaged building at 177 south highland. The service to this building was immediately turned off and isolated. The electric control center was contacted to de-energize the area at 1234. 258 were affected. Gas main valves were identified and closed to isolate the area affecting 33 customers. Upon investigation of the incident, it was discovered that a maintenance worker contracted by nyack college was performing some grading of the property behind 154 south highland, the bowmaan gym the morning of the explosion. This worker, using a backhoe, pulled on the 2" steel gas service for the bowman gym causing it to pull from a connecting coupling causing gas to leak. The gas then migrated through a storm drain into the sewer system that was connected to the sky island lodge. An uncapped, open sewer trap was discovered in the basement of the sky island lodge. This was deemed the point of entry into the building for the gas. The explosion occurred shortly thereafter.
Detailed record list
Occurred At
2013-06-04 11:55:00
Year
2013
Report Received Date
2013-07-03 00:00:00
Iyear
2013.0
Report Number
20130082.0
Supplemental Number
16720.0
Report Type
Supplemental Final
Operator Id
Name
Orange & Rockland Utility Inc
Operator Street Address
One Blue Hill Plaza
Operator City Name
Pearl River
Operator State Abbreviation
NY
Operator Postal Code
10965
Local Datetime
2013-06-04 11:55:00
Location Street Address
177 South Highland Avenue
Location City Name
Nyack
Location County Name
Rockland
Location State Abbreviation
NY
Location Postal Code
10960
Location Latitude
Location Longitude
Nrc Rpt Datetime
2013-06-04 14:03:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
0.1
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
1
Num Worker Injuries
0
Num Gp Injuries
7
Injure
8
Ignite Ind
No
Explode Ind
Yes
Num Pub Evacuated
0.0
Incident Identified Datetime
2013-06-04 11:55:00
On Site Datetime
2013-06-04 12:05:00
Federal
No
Location Type
Private Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Service
Installation Year
1969.0
Pipe Diameter
2.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Release Type
Leak
Leak Type
Other
Leak Type Other
Pipe Pulled From Coupling
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
0.0
Est Cost Emergency
75000.0
Est Cost Other
0.0
Est Cost Unintentional Release
0.0
Prpty
75000.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
33.0
Accident Psig
60.0
Normal Psig
60.0
Mop Psig
80.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The incident was caused by contractor damage to pipeline.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
No
Notify Cga Dirt
No
Private Row Ind
Yes
Private Subtype
Private Business
Excavator Type
Contractor
Excavator Equipment
Backhoe/trackhoe
Work Performed
Grading
One Call Notified Ind
No
Locator Type
Utility Owner
Visible Marks
No
Service Interruption
Yes
Service Interruption Hours
6.0
Root Cause Category
Excavation Issue
Root Cause Type
Improper Backfilling Practices
Preparer Name
A**** S*****
Preparer Title
Senior Engineer
Preparer Email
S******@o**.com
Preparer Telephone
845-577-3024
Authorizer Name
G*** F****
Authorizer Title
Principal Engineer
Authorizer Telephone
845-577-3537
Authorizer Email
F*****@o**.com
Narrative
Nyack college is a campus comprised of multiple buildings. Orange & rockland utilities provides natural gas and electric services to a number of the buildings including 177 south highland avenue known as sky island lodge and 154 south highland avenue known as bowman gymnasium. On tuesday, june 4, 2013 at approxiamately 1155 the gas emergency response center (gerc) received a call from rockland county fire control of a gas explosion at the sky island lodge. Gerc immediately dispatched all available units. The first two responders arrived at 1205 and 1206 respectively. A strong odor of gas was present in the air and gas vapors could be seen coming from the sewer clean out located along the curbline of 177 south highland avenue, the sky island lodge. The o&r servicemen immediately began a leak investigation. High concentrations of gas were detected in the outdoor sewer clean-outs, catch basin and sewer manhole. There were no gas readings in the test points taken in the earth. Covers on the sewer clean outs and manholes were removed allowing these structures to vent. At 1211, a 7% gas-in-air reading was recorded in atmoshere inside the damaged building at 177 south highland. The service to this building was immediately turned off and isolated. The electric control center was contacted to de-energize the area at 1234. 258 were affected. Gas main valves were identified and closed to isolate the area affecting 33 customers. Upon investigation of the incident, it was discovered that a maintenance worker contracted by nyack college was performing some grading of the property behind 154 south highland, the bowmaan gym the morning of the explosion. This worker, using a backhoe, pulled on the 2" steel gas service for the bowman gym causing it to pull from a connecting coupling causing gas to leak. The gas then migrated through a storm drain into the sewer system that was connected to the sky island lodge. An uncapped, open sewer trap was discovered in the basement of the sky island lodge. This was deemed the point of entry into the building for the gas. The explosion occurred shortly thereafter.
Occurred At 2013-06-04 11:55:00
Year 2013
Report Received Date 2013-07-03 00:00:00
Iyear 2013.0
Report Number 20130082.0
Supplemental Number 16720.0
Report Type Supplemental Final
Operator Id 14330 PHMSA Enforcement
Name Orange & Rockland Utility Inc
Operator Street Address One Blue Hill Plaza
Operator City Name Pearl River
Operator State Abbreviation NY
Operator Postal Code 10965
Local Datetime 2013-06-04 11:55:00
Location Street Address 177 South Highland Avenue
Location City Name Nyack
Location County Name Rockland
Location State Abbreviation NY
Location Postal Code 10960
Location Latitude 41.087078 Google Maps OpenStreetMap
Location Longitude -73.931658 Google Maps OpenStreetMap
Nrc Rpt Datetime 2013-06-04 14:03:00
Nrc Rpt Num 1049258 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 0.1
Fatality Ind No
Fatal 0
Injury Ind Yes
Num Emp Injuries 0
Num Contr Injuries 0
Num Er Injuries 1
Num Worker Injuries 0
Num Gp Injuries 7
Injure 8
Ignite Ind No
Explode Ind Yes
Num Pub Evacuated 0.0
Incident Identified Datetime 2013-06-04 11:55:00
On Site Datetime 2013-06-04 12:05:00
Federal No
Location Type Private Property
Incident Area Type Aboveground
Incident Area Subtype Inside A Building
Crossing No
Pipe Facility Type Privately Owned
System Part Involved Service
Installation Year 1969.0
Pipe Diameter 2.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Steel
Steel Seam Type Other
Steel Seam Type Details Unknown
Release Type Leak
Leak Type Other
Leak Type Other Pipe Pulled From Coupling
Class Location Type Class 3 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 0.0
Est Cost Emergency 75000.0
Est Cost Other 0.0
Est Cost Unintentional Release 0.0
Prpty 75000.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 33.0
Accident Psig 60.0
Normal Psig 60.0
Mop Psig 80.0
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Notification From Emergency Responder
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The incident was caused by contractor damage to pipeline.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Excavation Damage By Third Party
Ex Party Type Excavation Damage By Third Party
Prior Notification Ind No
Notify Cga Dirt No
Private Row Ind Yes
Private Subtype Private Business
Excavator Type Contractor
Excavator Equipment Backhoe/trackhoe
Work Performed Grading
One Call Notified Ind No
Locator Type Utility Owner
Visible Marks No
Service Interruption Yes
Service Interruption Hours 6.0
Root Cause Category Excavation Issue
Root Cause Type Improper Backfilling Practices
Preparer Name A**** S*****
Preparer Title Senior Engineer
Preparer Email S******@o**.com
Preparer Telephone 845-577-3024
Authorizer Name G*** F****
Authorizer Title Principal Engineer
Authorizer Telephone 845-577-3537
Authorizer Email F*****@o**.com
Narrative Nyack college is a campus comprised of multiple buildings. Orange & rockland utilities provides natural gas and electric services to a number of the buildings including 177 south highland avenue known as sky island lodge and 154 south highland avenue known as bowman gymnasium. On tuesday, june 4, 2013 at approxiamately 1155 the gas emergency response center (gerc) received a call from rockland county fire control of a gas explosion at the sky island lodge. Gerc immediately dispatched all available units. The first two responders arrived at 1205 and 1206 respectively. A strong odor of gas was present in the air and gas vapors could be seen coming from the sewer clean out located along the curbline of 177 south highland avenue, the sky island lodge. The o&r servicemen immediately began a leak investigation. High concentrations of gas were detected in the outdoor sewer clean-outs, catch basin and sewer manhole. There were no gas readings in the test points taken in the earth. Covers on the sewer clean outs and manholes were removed allowing these structures to vent. At 1211, a 7% gas-in-air reading was recorded in atmoshere inside the damaged building at 177 south highland. The service to this building was immediately turned off and isolated. The electric control center was contacted to de-energize the area at 1234. 258 were affected. Gas main valves were identified and closed to isolate the area affecting 33 customers. Upon investigation of the incident, it was discovered that a maintenance worker contracted by nyack college was performing some grading of the property behind 154 south highland, the bowmaan gym the morning of the explosion. This worker, using a backhoe, pulled on the 2" steel gas service for the bowman gym causing it to pull from a connecting coupling causing gas to leak. The gas then migrated through a storm drain into the sewer system that was connected to the sky island lodge. An uncapped, open sewer trap was discovered in the basement of the sky island lodge. This was deemed the point of entry into the building for the gas. The explosion occurred shortly thereafter.