GD incident on 2010-11-18 — NY

Operator
Consolidated Edison Co Of New York
Cause
Equipment Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$15,147
Incident datetime
2010-11-18 13:48
Report number
Location
NY, WESTCHESTER
Narrative
On 11-18-10 at 12:39 hrs leak survey notified the gas emergency response center (gerc) of a strong odor at 144 bradhurst ave., mt. Pleasant. A code murre was initiated and the mt. Pleasant fire dept. (mpfd), gas distribution services (gds), gas construction and westchester gas operations supervision were dispatched. All buildings in the area checked were found to be free of gas readings (aka- clear) with the assist of mpfd, and subsurface structures in the area were also clear. After investigating over the 12" high pressure pe main and the 12" transmission steel main it was determined the leak was on the transmission main which supplies regulator station gr-484 at brighton and newman aves. Regulator stations gr-519, 673 and 483 were raised to compensate for loss of gr-484. Gds crews were dispatched to v-31585. Gas control, pressure control were notified, and westr general mgr. Thaker & chief transmission engineer payne were advised and responded. V-31585 was closed at 1426 hrs and gas control reported no system impact. V-31587 was closed as a contingency and no system impact resulted. Transmission pressure was reduced to high pressure (60 psi) and the transmission main was excavated over the highest reading. Construction found a leak on a 12" compression coupling and a welded repair sleeve was installed over the coupling. The sleeve was installed on 11-19-10 and at 14:16 hrs mv-31587 was fully opened, at 1459 mv-31585 was fully opened and regulator station gr-484 was placed back in service by pressure control. The US DOT and nys psc were notified. This was a serious level event. Note--this gas distribution incident report is generated to replace rescinded gas transmission incident report 20100100-15165
Detailed record list
Occurred At
2010-11-18 13:48:00
Year
2010
Report Received Date
2013-05-22 00:00:00
Iyear
2010.0
Report Number
20130057.0
Supplemental Number
15664.0
Report Type
Original Final
Operator Id
Name
Consolidated Edison Co Of New York
Operator Street Address
4 Irving Place
Operator City Name
New York
Operator State Abbreviation
NY
Operator Postal Code
10003
Local Datetime
2010-11-18 13:48:00
Location Street Address
144 Bradhurst Avenue
Location City Name
Mount Pleasant
Location County Name
Westchester
Location State Abbreviation
NY
Location Postal Code
10532-1625
Location Latitude
Location Longitude
Nrc Rpt Datetime
2010-11-18 14:19:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
105.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2010-11-18 13:48:00
On Site Datetime
2010-11-18 13:48:00
Federal
No
Location Type
Utility Right-Of-Way / Easement
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
42.0
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Other
System Part Details
Onshore Pipeline, Including Valve Sites
Installation Year
1949.0
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Release Type
Leak
Leak Type
Seal Or Packing
Class Location Type
Class 4 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
15147.0
Est Cost Emergency
3168.0
Est Cost Other
1400.0
Est Cost Other Details
Materials
Est Cost Unintentional Release
100.0
Prpty
19815.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
215.0
Normal Psig
215.0
Mop Psig
245.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Other
Other Non Threaded Details
Mechanical Compression Coupling Leak
Preparer Name
K**** F****
Preparer Title
Manager-Gas Emergency Response Center
Preparer Email
F*****@c****.com
Preparer Telephone
718-319-2310
Preparer Fax
718-904-4607
Authorizer Name
V***** D******
Authorizer Title
Dept. Manager-Gas Emergency Response Center
Authorizer Telephone
718-319-2310
Authorizer Email
D******@c****.com
Narrative
On 11-18-10 at 12:39 hrs leak survey notified the gas emergency response center (gerc) of a strong odor at 144 bradhurst ave., mt. Pleasant. A code murre was initiated and the mt. Pleasant fire dept. (mpfd), gas distribution services (gds), gas construction and westchester gas operations supervision were dispatched. All buildings in the area checked were found to be free of gas readings (aka- clear) with the assist of mpfd, and subsurface structures in the area were also clear. After investigating over the 12" high pressure pe main and the 12" transmission steel main it was determined the leak was on the transmission main which supplies regulator station gr-484 at brighton and newman aves. Regulator stations gr-519, 673 and 483 were raised to compensate for loss of gr-484. Gds crews were dispatched to v-31585. Gas control, pressure control were notified, and westr general mgr. Thaker & chief transmission engineer payne were advised and responded. V-31585 was closed at 1426 hrs and gas control reported no system impact. V-31587 was closed as a contingency and no system impact resulted. Transmission pressure was reduced to high pressure (60 psi) and the transmission main was excavated over the highest reading. Construction found a leak on a 12" compression coupling and a welded repair sleeve was installed over the coupling. The sleeve was installed on 11-19-10 and at 14:16 hrs mv-31587 was fully opened, at 1459 mv-31585 was fully opened and regulator station gr-484 was placed back in service by pressure control. The US DOT and nys psc were notified. This was a serious level event. Note--this gas distribution incident report is generated to replace rescinded gas transmission incident report 20100100-15165
Occurred At 2010-11-18 13:48:00
Year 2010
Report Received Date 2013-05-22 00:00:00
Iyear 2010.0
Report Number 20130057.0
Supplemental Number 15664.0
Report Type Original Final
Operator Id 2704 PHMSA Enforcement
Name Consolidated Edison Co Of New York
Operator Street Address 4 Irving Place
Operator City Name New York
Operator State Abbreviation NY
Operator Postal Code 10003
Local Datetime 2010-11-18 13:48:00
Location Street Address 144 Bradhurst Avenue
Location City Name Mount Pleasant
Location County Name Westchester
Location State Abbreviation NY
Location Postal Code 10532-1625
Location Latitude 41.095645 Google Maps OpenStreetMap
Location Longitude -73.802806 Google Maps OpenStreetMap
Nrc Rpt Datetime 2010-11-18 14:19:00
Nrc Rpt Num 960220 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 105.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0.0
Incident Identified Datetime 2010-11-18 13:48:00
On Site Datetime 2010-11-18 13:48:00
Federal No
Location Type Utility Right-Of-Way / Easement
Incident Area Type Underground
Incident Area Subtype Under Pavement
Depth Of Cover 42.0
Crossing No
Pipe Facility Type Privately Owned
System Part Involved Other
System Part Details Onshore Pipeline, Including Valve Sites
Installation Year 1949.0
Material Involved Steel
Steel Seam Type Other
Steel Seam Type Details Unknown
Release Type Leak
Leak Type Seal Or Packing
Class Location Type Class 4 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 15147.0
Est Cost Emergency 3168.0
Est Cost Other 1400.0
Est Cost Other Details Materials
Est Cost Unintentional Release 100.0
Prpty 19815.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 0.0
Accident Psig 215.0
Normal Psig 215.0
Mop Psig 245.0
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind Other
Other Non Threaded Details Mechanical Compression Coupling Leak
Preparer Name K**** F****
Preparer Title Manager-Gas Emergency Response Center
Preparer Email F*****@c****.com
Preparer Telephone 718-319-2310
Preparer Fax 718-904-4607
Authorizer Name V***** D******
Authorizer Title Dept. Manager-Gas Emergency Response Center
Authorizer Telephone 718-319-2310
Authorizer Email D******@c****.com
Narrative On 11-18-10 at 12:39 hrs leak survey notified the gas emergency response center (gerc) of a strong odor at 144 bradhurst ave., mt. Pleasant. A code murre was initiated and the mt. Pleasant fire dept. (mpfd), gas distribution services (gds), gas construction and westchester gas operations supervision were dispatched. All buildings in the area checked were found to be free of gas readings (aka- clear) with the assist of mpfd, and subsurface structures in the area were also clear. After investigating over the 12" high pressure pe main and the 12" transmission steel main it was determined the leak was on the transmission main which supplies regulator station gr-484 at brighton and newman aves. Regulator stations gr-519, 673 and 483 were raised to compensate for loss of gr-484. Gds crews were dispatched to v-31585. Gas control, pressure control were notified, and westr general mgr. Thaker & chief transmission engineer payne were advised and responded. V-31585 was closed at 1426 hrs and gas control reported no system impact. V-31587 was closed as a contingency and no system impact resulted. Transmission pressure was reduced to high pressure (60 psi) and the transmission main was excavated over the highest reading. Construction found a leak on a 12" compression coupling and a welded repair sleeve was installed over the coupling. The sleeve was installed on 11-19-10 and at 14:16 hrs mv-31587 was fully opened, at 1459 mv-31585 was fully opened and regulator station gr-484 was placed back in service by pressure control. The US DOT and nys psc were notified. This was a serious level event. Note--this gas distribution incident report is generated to replace rescinded gas transmission incident report 20100100-15165