Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2013-02-27 — MI
Operator
Consumers Energy Co
Cause
Miscellaneous Root Causes
Commodity
Natural Gas
Program
GD
Damage and Injuries
1 fatality
0 injuries
Property damage (nominal)
$1,000
Incident datetime
2013-02-27 17:07
Report number
Location
MI, OAKLAND
Narrative
At approximately 1707 hours (5:07 pm) on february 27, 2013, an explosion occurred at 4232 cooper avenue, royal oak, michigan. Consumers energy management and field personnel arrived at the site at various times between 1715 and 1809 in response to the incident. Working with local police and fire departments, consumers energy excavated and shut off the gas supply to 4232 cooper ave at 1836 hours. Information obtained from the incident review and investigation determined that the crews did not follow company boring procedures during installation of a new main along cooper avenue. As a result, the operation caused damage to the steel gas service located at 4232 cooper avenue in royal oak, michigan, resulting in possible below-grade gas migration into the structure. Investigation established that crews did not follow consumers energy procedural requirements to excavate and expose all active services prior to performing boring operations. These crews also failed to follow company gas leak response standards. Note (5/15/2013 supplemental report): despite the nearby facilities being staked correctly (part g3-12) and locate marks being visible within the vicinity of the boring area (part g3-11), following the incident there was minimal observation of staking flags or paint marking at some service locations along cooper avenue. That marking was not immediately apparent during post-incident observations may be due in part to large amounts of debris in the area (as well as recent snowfall) partially obstructing direct observation of all facility staking along cooper avenue.
Detailed record list
Occurred At
2013-02-27 17:07:00
Year
2013
Report Received Date
2013-03-28 00:00:00
Iyear
2013.0
Report Number
20130033.0
Supplemental Number
15656.0
Report Type
Supplemental Final
Operator Id
2748
Name
Consumers Energy Co
Operator Street Address
One Energy Plaza
Operator City Name
Jackson
Operator State Abbreviation
MI
Operator Postal Code
49201
Local Datetime
2013-02-27 17:07:00
Location Street Address
4232 Cooper Avenue
Location City Name
Royal Oak
Location County Name
Oakland
Location State Abbreviation
MI
Location Postal Code
48073
Location Latitude
42.527098
Location Longitude
-83.19306
Nrc Rpt Datetime
2013-02-27 19:01:00
Nrc Rpt Num
1039624
Commodity Released Type
Natural Gas
Unintentional Release
231.8
Fatality Ind
Yes
Num Emp Fatalities
0
Num Contr Fatalities
0
Num Er Fatalities
0
Num Worker Fatalities
0
Num Gp Fatalities
1
Fatal
1
Injury Ind
No
Injure
0
Ignite Ind
Yes
Explode Ind
Yes
Num Pub Evacuated
75.0
Incident Identified Datetime
2013-02-27 17:07:00
On Site Datetime
2013-02-27 17:15:00
Federal
No
Location Type
Private Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Service
Installation Year
1948.0
Pipe Diameter
0.75
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Wt Steel
0.113
Release Type
Mechanical Puncture
Puncture Axial
1.2
Puncture Circum
0.5
Class Location Type
Class 3 Location
Est Cost Oper Paid
750000.0
Est Cost Prop Damage
1000.0
Est Cost Emergency
19336.0
Est Cost Other
3000.0
Est Cost Other Details
Hotel Accomodations For Evacuated Customers
Est Cost Unintentional Release
2133.0
Prpty
775469.0
Commercial Affected
2.0
Industrial Affected
0.0
Residences Affected
36.0
Accident Psig
55.0
Normal Psig
55.0
Mop Psig
60.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Other
Accident Details
Operator Personnel Felt Explosion From Nearby Royal Oak Service Center
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
Yes
Num Employees Tested
7
Num Employees Failed
0
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Operator (First Party)
Ex Party Type
Excavation Damage By Operator (First Party)
Notify Cga Dirt
Yes
Public Row Ind
Yes
Public Subtype
City Street
Pipeline Easement Row Ind
Yes
Excavator Type
Utility
Excavator Equipment
Boring
Work Performed
Natural Gas
One Call Notified Ind
Yes
One Call Ticket Num
30380079
Locator Type
Utility Owner
Visible Marks
Yes
Service Interruption
Yes
Service Interruption Hours
51.0
Root Cause Category
Miscellaneous Root Causes
Root Cause Type
Root Cause Not Listed (Comment Required)
Root Cause Type Other
Crews Did Not Follow Procedures.
Preparer Name
A*** M* C*********
Preparer Title
Gas Regulatory Services Engineer
Preparer Email
A**************@c********.com
Preparer Telephone
989-791-5841
Authorizer Name
T**** A* G****
Authorizer Title
Regulatory And Compliance Manager
Authorizer Telephone
517-768-3187
Authorizer Email
T**********@c********.com
Narrative
At approximately 1707 hours (5:07 pm) on february 27, 2013, an explosion occurred at 4232 cooper avenue, royal oak, michigan. Consumers energy management and field personnel arrived at the site at various times between 1715 and 1809 in response to the incident. Working with local police and fire departments, consumers energy excavated and shut off the gas supply to 4232 cooper ave at 1836 hours. Information obtained from the incident review and investigation determined that the crews did not follow company boring procedures during installation of a new main along cooper avenue. As a result, the operation caused damage to the steel gas service located at 4232 cooper avenue in royal oak, michigan, resulting in possible below-grade gas migration into the structure. Investigation established that crews did not follow consumers energy procedural requirements to excavate and expose all active services prior to performing boring operations. These crews also failed to follow company gas leak response standards. Note (5/15/2013 supplemental report): despite the nearby facilities being staked correctly (part g3-12) and locate marks being visible within the vicinity of the boring area (part g3-11), following the incident there was minimal observation of staking flags or paint marking at some service locations along cooper avenue. That marking was not immediately apparent during post-incident observations may be due in part to large amounts of debris in the area (as well as recent snowfall) partially obstructing direct observation of all facility staking along cooper avenue.
| Occurred At | 2013-02-27 17:07:00 |
|---|---|
| Year | 2013 |
| Report Received Date | 2013-03-28 00:00:00 |
| Iyear | 2013.0 |
| Report Number | 20130033.0 |
| Supplemental Number | 15656.0 |
| Report Type | Supplemental Final |
| Operator Id | 2748 PHMSA Enforcement |
| Name | Consumers Energy Co |
| Operator Street Address | One Energy Plaza |
| Operator City Name | Jackson |
| Operator State Abbreviation | MI |
| Operator Postal Code | 49201 |
| Local Datetime | 2013-02-27 17:07:00 |
| Location Street Address | 4232 Cooper Avenue |
| Location City Name | Royal Oak |
| Location County Name | Oakland |
| Location State Abbreviation | MI |
| Location Postal Code | 48073 |
| Location Latitude | 42.527098 Google Maps OpenStreetMap |
| Location Longitude | -83.19306 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2013-02-27 19:01:00 |
| Nrc Rpt Num | 1039624 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 231.8 |
| Fatality Ind | Yes |
| Num Emp Fatalities | 0 |
| Num Contr Fatalities | 0 |
| Num Er Fatalities | 0 |
| Num Worker Fatalities | 0 |
| Num Gp Fatalities | 1 |
| Fatal | 1 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Explode Ind | Yes |
| Num Pub Evacuated | 75.0 |
| Incident Identified Datetime | 2013-02-27 17:07:00 |
| On Site Datetime | 2013-02-27 17:15:00 |
| Federal | No |
| Location Type | Private Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Inside A Building |
| Crossing | No |
| Pipe Facility Type | Privately Owned |
| System Part Involved | Service |
| Installation Year | 1948.0 |
| Pipe Diameter | 0.75 |
| Pipe Specification | Unknown |
| Pipe Manufacturer | Unknown |
| Material Involved | Steel |
| Wt Steel | 0.113 |
| Release Type | Mechanical Puncture |
| Puncture Axial | 1.2 |
| Puncture Circum | 0.5 |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 750000.0 |
| Est Cost Prop Damage | 1000.0 |
| Est Cost Emergency | 19336.0 |
| Est Cost Other | 3000.0 |
| Est Cost Other Details | Hotel Accomodations For Evacuated Customers |
| Est Cost Unintentional Release | 2133.0 |
| Prpty | 775469.0 |
| Commercial Affected | 2.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 36.0 |
| Accident Psig | 55.0 |
| Normal Psig | 55.0 |
| Mop Psig | 60.0 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Scada In Place Ind | No |
| Accident Identifier | Other |
| Accident Details | Operator Personnel Felt Explosion From Nearby Royal Oak Service Center |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | Yes |
| Num Employees Tested | 7 |
| Num Employees Failed | 0 |
| Contractor Drug Test Ind | No |
| Cause | Excavation Damage |
| Cause Details | Excavation Damage By Operator (First Party) |
| Ex Party Type | Excavation Damage By Operator (First Party) |
| Notify Cga Dirt | Yes |
| Public Row Ind | Yes |
| Public Subtype | City Street |
| Pipeline Easement Row Ind | Yes |
| Excavator Type | Utility |
| Excavator Equipment | Boring |
| Work Performed | Natural Gas |
| One Call Notified Ind | Yes |
| One Call Ticket Num | 30380079 |
| Locator Type | Utility Owner |
| Visible Marks | Yes |
| Service Interruption | Yes |
| Service Interruption Hours | 51.0 |
| Root Cause Category | Miscellaneous Root Causes |
| Root Cause Type | Root Cause Not Listed (Comment Required) |
| Root Cause Type Other | Crews Did Not Follow Procedures. |
| Preparer Name | A*** M* C********* |
| Preparer Title | Gas Regulatory Services Engineer |
| Preparer Email | A**************@c********.com |
| Preparer Telephone | 989-791-5841 |
| Authorizer Name | T**** A* G**** |
| Authorizer Title | Regulatory And Compliance Manager |
| Authorizer Telephone | 517-768-3187 |
| Authorizer Email | T**********@c********.com |
| Narrative | At approximately 1707 hours (5:07 pm) on february 27, 2013, an explosion occurred at 4232 cooper avenue, royal oak, michigan. Consumers energy management and field personnel arrived at the site at various times between 1715 and 1809 in response to the incident. Working with local police and fire departments, consumers energy excavated and shut off the gas supply to 4232 cooper ave at 1836 hours. Information obtained from the incident review and investigation determined that the crews did not follow company boring procedures during installation of a new main along cooper avenue. As a result, the operation caused damage to the steel gas service located at 4232 cooper avenue in royal oak, michigan, resulting in possible below-grade gas migration into the structure. Investigation established that crews did not follow consumers energy procedural requirements to excavate and expose all active services prior to performing boring operations. These crews also failed to follow company gas leak response standards. Note (5/15/2013 supplemental report): despite the nearby facilities being staked correctly (part g3-12) and locate marks being visible within the vicinity of the boring area (part g3-11), following the incident there was minimal observation of staking flags or paint marking at some service locations along cooper avenue. That marking was not immediately apparent during post-incident observations may be due in part to large amounts of debris in the area (as well as recent snowfall) partially obstructing direct observation of all facility staking along cooper avenue. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company