Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2012-05-14 — OK
Operator
Magellan Terminals Holdings, Lp
Cause
Material Failure Of Pipe Or Weld
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$10,000
Incident datetime
2012-05-14 07:00
Report number
Location
OK
Narrative
At 0700 on 5/14/12, an operator discovered oil on a containment pond that came throught the external floating roof drain. The roof drain valve was closed to isolate the leak source and contractors were contacted. After further investigation it was determined that a reinforcing pad around a roof support leg began to leak due to a weld defect. It was later determined that the tank needed to be taken out of service and cleaned to be repaired. Repairs included grinding out the weld and re-welding the repad. They also welded the underside of the repad as well to ensure the repair of the leak. A dye test was performed for verification. The cost exceeded the $50,000 criteria due to the $112,000 to clean the tank and external roof.
Detailed record list
Report Received Date
2012-06-13 00:00:00
Iyear
2012
Report Number
20120181
Supplemental Number
17840
Report Type
Supplemental Final
Operator Id
31580
Name
Magellan Terminals Holdings, Lp
Operator Street Address
100 West 5th Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2012-05-14 07:00:00
Location Latitude
35.92536
Location Longitude
-96.74162
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.71
Intentional Release Bbls
0
Recovered Bbls
0.71
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2012-05-14 07:00:00
System Part Involved
Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore
Onshore
On Site Datetime
2012-05-14 07:00:00
Nrc Rpt Datetime
2012-06-12 06:18:00
Nrc Rpt Num
1014367
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
South Cushing Crude
Segment Name
Tank #2511
Onshore State Abbreviation
Ok
Onshore Postal Code
74023
Onshore City Name
Cushing
Onshore County Name
Adair
Designated Location
Milepost/valve Station
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Tank, Including Attached Appurtenances
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Weld, Including Heat-Affected Zone
Weld Subtype
Fillet Weld
Tank Type
Atmospheric
Installation Year
2011
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
10000
Est Cost Emergency
3000
Est Cost Environmental
0
Est Cost Other
112000
Est Cost Other Details
Cost Of Cleaning The Tank For Repairs And Cleaning Off External Floating Roof
Prpty
125000
Accident Psig
3
Mop Psig
275
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
This was a roof drain / reinforcing pad around a supporting roof leg and amount was under the detectable limits for a controller to detect.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Material Failure Of Pipe Or Weld
Cause Details
Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind
Yes
Failure Type
Design-, Construction-, Installation-, Or Fabrication-Related
Other Factor
Yes
Other Factor Details
Weld Quality
Additional Lack Fusion Ind
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
Yes
Exm Other Type
At Time Of Repair Of The Support Leg Reinforcement Pad A Diesel Test Was Performed For The Top Weld And Then A Dye Penetrant Test Was Performed After The Underside Weld Was Completed.
Exm Other Rcnt Year
2012
Exm Other Rcnt Ind
Yes
Preparer Name
D******* C*********
Preparer Title
Compliance Coordinator Sr
Preparer Email
D******************@m*********.com
Prepared Date
2013-04-08 00:00:00
Authorizer Name
D******* C*********
Authorizer Telephone
9185747386
Authorizer Email
No Email Address
Narrative
At 0700 on 5/14/12, an operator discovered oil on a containment pond that came throught the external floating roof drain. The roof drain valve was closed to isolate the leak source and contractors were contacted. After further investigation it was determined that a reinforcing pad around a roof support leg began to leak due to a weld defect. It was later determined that the tank needed to be taken out of service and cleaned to be repaired. Repairs included grinding out the weld and re-welding the repad. They also welded the underside of the repad as well to ensure the repair of the leak. A dye test was performed for verification. The cost exceeded the $50,000 criteria due to the $112,000 to clean the tank and external roof.
| Report Received Date | 2012-06-13 00:00:00 |
|---|---|
| Iyear | 2012 |
| Report Number | 20120181 |
| Supplemental Number | 17840 |
| Report Type | Supplemental Final |
| Operator Id | 31580 PHMSA Enforcement |
| Name | Magellan Terminals Holdings, Lp |
| Operator Street Address | 100 West 5th Street |
| Operator City Name | Tulsa |
| Operator State Abbreviation | OK |
| Operator Postal Code | 74103 |
| Local Datetime | 2012-05-14 07:00:00 |
| Location Latitude | 35.92536 Google Maps OpenStreetMap |
| Location Longitude | -96.74162 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 0.71 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0.71 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2012-05-14 07:00:00 |
| System Part Involved | Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances |
| On Off Shore | Onshore |
| On Site Datetime | 2012-05-14 07:00:00 |
| Nrc Rpt Datetime | 2012-06-12 06:18:00 |
| Nrc Rpt Num | 1014367 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | South Cushing Crude |
| Segment Name | Tank #2511 |
| Onshore State Abbreviation | Ok |
| Onshore Postal Code | 74023 |
| Onshore City Name | Cushing |
| Onshore County Name | Adair |
| Designated Location | Milepost/valve Station |
| Designated Name | 0 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Tank, Including Attached Appurtenances |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Weld, Including Heat-Affected Zone |
| Weld Subtype | Fillet Weld |
| Tank Type | Atmospheric |
| Installation Year | 2011 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 10000 |
| Est Cost Emergency | 3000 |
| Est Cost Environmental | 0 |
| Est Cost Other | 112000 |
| Est Cost Other Details | Cost Of Cleaning The Tank For Repairs And Cleaning Off External Floating Roof |
| Prpty | 125000 |
| Accident Psig | 3 |
| Mop Psig | 275 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | This was a roof drain / reinforcing pad around a supporting roof leg and amount was under the detectable limits for a controller to detect. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Material Failure Of Pipe Or Weld |
| Cause Details | Design-, Construction-, Installation-, Or Fabrication-Related |
| Field Exam Ind | Yes |
| Failure Type | Design-, Construction-, Installation-, Or Fabrication-Related |
| Other Factor | Yes |
| Other Factor Details | Weld Quality |
| Additional Lack Fusion Ind | Yes |
| Collected Data Ind | No |
| Has Hydrtst Conduc Before Ind | No |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | Yes |
| Exm Other Type | At Time Of Repair Of The Support Leg Reinforcement Pad A Diesel Test Was Performed For The Top Weld And Then A Dye Penetrant Test Was Performed After The Underside Weld Was Completed. |
| Exm Other Rcnt Year | 2012 |
| Exm Other Rcnt Ind | Yes |
| Preparer Name | D******* C********* |
| Preparer Title | Compliance Coordinator Sr |
| Preparer Email | D******************@m*********.com |
| Prepared Date | 2013-04-08 00:00:00 |
| Authorizer Name | D******* C********* |
| Authorizer Telephone | 9185747386 |
| Authorizer Email | No Email Address |
| Narrative | At 0700 on 5/14/12, an operator discovered oil on a containment pond that came throught the external floating roof drain. The roof drain valve was closed to isolate the leak source and contractors were contacted. After further investigation it was determined that a reinforcing pad around a roof support leg began to leak due to a weld defect. It was later determined that the tank needed to be taken out of service and cleaned to be repaired. Repairs included grinding out the weld and re-welding the repad. They also welded the underside of the repad as well to ensure the repair of the leak. A dye test was performed for verification. The cost exceeded the $50,000 criteria due to the $112,000 to clean the tank and external roof. |