HL incident on 2011-11-07 — TX

Operator
Plains Pipeline, L.p.
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$1,500
Incident datetime
2011-11-07 07:00
Report number
Location
TX
Narrative
At approximately 6:00 am on november 7, 2011, a contractor working for plains observed product on the ground at the odessa station. The tank maintenance supervisor was notified and the valves associated with the pipeline that connects to the discharge meter case were closed to isolate the release. Remediation efforts began immediately following the notification to the maintenance supervisor. Based on the chemical analysis report, the failure was due to internal corrosion from stagnant fluid around the drain of the discharge meter case allowing bacteria to coalesce and form a bacterial colony, resulting in sulfate reducing bacterial corrosion. Bacterial corrosion was found at the bottom of the discharge meter case. The meter case was replaced and will be drained monthly to minimize the possibility of recurrence.
Detailed record list
Report Received Date
2011-12-05 00:00:00
Iyear
2011
Report Number
20110433
Supplemental Number
17669
Report Type
Supplemental Final
Operator Id
Name
Plains Pipeline, L.p.
Operator Street Address
333 Clay Street, Suite 1900
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2011-11-07 06:00:00
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
80
Recovered Bbls
80
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Incident Identified Datetime
2011-11-07 07:00:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Meter Was Not Operating At The Time Of The Incident
On Site Datetime
2011-11-07 07:20:00
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Odessa Station
Segment Name
Odessa Basin Delivery Line
Onshore State Abbreviation
Tx
Onshore Postal Code
79764
Onshore City Name
Odessa
Onshore County Name
Ector
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Meter/prover
Installation Year
2003
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
1900
Est Cost Prop Damage
1500
Est Cost Emergency
5000
Est Cost Environmental
35000
Est Cost Other
0
Prpty
43400
Accident Psig
30
Mop Psig
30
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Meter was not operating at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Microbiological Ind
Yes
Int Other Basis Ind
Yes
Int Corrosion Basis Details
Chemical Analysis Report
Int Other Loc Ind
Yes
Corrosion Location Details
Discharge Meter Case
Corrosion Inhibitors
Yes
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
No
Preparer Name
S***** N*****
Preparer Title
Compliance Specialist
Preparer Email
S******@p****.com
Preparer Telephone
713-993-5673
Preparer Fax
713-646-4310
Prepared Date
2013-03-25 00:00:00
Authorizer Name
J***** R J****
Authorizer Telephone
713-993-5162
Authorizer Title
Sr Director Env And Regulatory Compliance
Authorizer Email
J******@p****.com
Narrative
At approximately 6:00 am on november 7, 2011, a contractor working for plains observed product on the ground at the odessa station. The tank maintenance supervisor was notified and the valves associated with the pipeline that connects to the discharge meter case were closed to isolate the release. Remediation efforts began immediately following the notification to the maintenance supervisor. Based on the chemical analysis report, the failure was due to internal corrosion from stagnant fluid around the drain of the discharge meter case allowing bacteria to coalesce and form a bacterial colony, resulting in sulfate reducing bacterial corrosion. Bacterial corrosion was found at the bottom of the discharge meter case. The meter case was replaced and will be drained monthly to minimize the possibility of recurrence.
Report Received Date 2011-12-05 00:00:00
Iyear 2011
Report Number 20110433
Supplemental Number 17669
Report Type Supplemental Final
Operator Id 300 PHMSA Enforcement
Name Plains Pipeline, L.p.
Operator Street Address 333 Clay Street, Suite 1900
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2011-11-07 06:00:00
Location Latitude 31.89631 Google Maps OpenStreetMap
Location Longitude -102.56548 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 80
Recovered Bbls 80
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Contractor Working For The Operator
Incident Identified Datetime 2011-11-07 07:00:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Shutdown Due Accident Ind No
Shutdown Explain Meter Was Not Operating At The Time Of The Incident
On Site Datetime 2011-11-07 07:20:00
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Odessa Station
Segment Name Odessa Basin Delivery Line
Onshore State Abbreviation Tx
Onshore Postal Code 79764
Onshore City Name Odessa
Onshore County Name Ector
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Meter/prover
Installation Year 2003
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
Other Pop Ind Yes
Other Pop Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 1900
Est Cost Prop Damage 1500
Est Cost Emergency 5000
Est Cost Environmental 35000
Est Cost Other 0
Prpty 43400
Accident Psig 30
Mop Psig 30
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function < 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Meter was not operating at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results Localized Pitting
Int Microbiological Ind Yes
Int Other Basis Ind Yes
Int Corrosion Basis Details Chemical Analysis Report
Int Other Loc Ind Yes
Corrosion Location Details Discharge Meter Case
Corrosion Inhibitors Yes
Corrosion Lining No
Cleaning Dewatering Not Applicable - Not Mainline Pipe
Corrosion Coupons No
Preparer Name S***** N*****
Preparer Title Compliance Specialist
Preparer Email S******@p****.com
Preparer Telephone 713-993-5673
Preparer Fax 713-646-4310
Prepared Date 2013-03-25 00:00:00
Authorizer Name J***** R J****
Authorizer Telephone 713-993-5162
Authorizer Title Sr Director Env And Regulatory Compliance
Authorizer Email J******@p****.com
Narrative At approximately 6:00 am on november 7, 2011, a contractor working for plains observed product on the ground at the odessa station. The tank maintenance supervisor was notified and the valves associated with the pipeline that connects to the discharge meter case were closed to isolate the release. Remediation efforts began immediately following the notification to the maintenance supervisor. Based on the chemical analysis report, the failure was due to internal corrosion from stagnant fluid around the drain of the discharge meter case allowing bacteria to coalesce and form a bacterial colony, resulting in sulfate reducing bacterial corrosion. Bacterial corrosion was found at the bottom of the discharge meter case. The meter case was replaced and will be drained monthly to minimize the possibility of recurrence.