HL incident on 2011-10-06 — OK

Operator
Magellan Pipeline Company, Lp
Cause
Notification Issue
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$35,000
Incident datetime
2011-10-06 11:55
Report number
Location
OK
Narrative
At approximately 11:42 october 6, 2011 the scada system in magellan's operations control center indicted a sharp drop in pressure and an increase in flow rate on the #6-10" pipeline between topeka and kansas city. Magellan personnel executed a code red emergency shutdown of the line in accordance with magellan's o&m procedures and notified qualified field personnel to investigate. Subsequent investigation discovered that an excavating contractor had dented the line in several places and punctured it with a tooth of a front end loader while excavating a pond. The excavator did not place a one-call with the kansas one call agency. Magellan personnel immediately began controlling the released product and repaired the line with a segment of new, pretested pipe in accordance with PHMSA regulations and company procedures. The released product was recovered and 4708 cubic yards of effected soil were remediated per company and state requirements.
Detailed record list
Report Received Date
2011-11-04 00:00:00
Iyear
2011
Report Number
20110412
Supplemental Number
17121
Report Type
Supplemental Final
Operator Id
Name
Magellan Pipeline Company, Lp
Operator Street Address
100 West 5th Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2011-10-06 11:42:00
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
590
Intentional Release Bbls
0
Recovered Bbls
300
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Cpm Leak Detection System Or Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Calculations)
Incident Identified Datetime
2011-10-06 11:55:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2011-10-06 11:46:00
Restart Datetime
2011-10-07 15:12:00
On Site Datetime
2011-10-06 13:30:00
Nrc Rpt Datetime
2011-10-06 12:33:00
Nrc Rpt Num
Ignite Ind
No
Explode Ind
No
Upstream Valve Type Ind
Remotely Controlled
Downstream Valve Type Ind
Remotely Controlled
Pipe Fac Name
#6-10" Topeka To Kansas City Line
Segment Name
Line Segment #6110
Onshore State Abbreviation
Ks
Onshore Postal Code
66049
Onshore City Name
Lawrence
Onshore County Name
Douglas
Designated Location
Survey Station No.
Designated Name
6552+02
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
33
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
10.75
Pipe Wall Thickness
0.203
Pipe Smys
46000
Pipe Specification
Api 5lx-46
Pipe Seam Type
Erw - Low Frequency
Pipe Manufacturer
Youngstown Steel
Pipe Coating Type
Asphalt
Installation Year
1955
Manufactured Year
1955
Material Involved
Carbon Steel
Release Type
Mechanical Puncture
Puncture Axial
3.5
Puncture Circum
2
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
62300
Est Cost Prop Damage
35000
Est Cost Emergency
50000
Est Cost Environmental
520541
Est Cost Other
0
Prpty
667841
Accident Psig
230
Mop Psig
1150
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
262704
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
Yes
Cpm Conf Ind
Yes
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The release was the result of a third party line strike by an excavator and did not stem from the operation of the line
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
1
Num Employees Failed
0
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
No
Notify Cga Dirt
Yes
Private Row Ind
Yes
Private Subtype
Private Landowner
Pipeline Easement Row Ind
Yes
Excavator Type
Contractor
Excavator Equipment
Backhoe/trackhoe
Work Performed
Agriculture
One Call Notified Ind
No
Locator Type
Unknown/other
Visible Marks
No
Service Interruption
Yes
Service Interruption Hours
27
Root Cause Category
Notification Issue
Root Cause Type
No Notification Made To The One-Call Center/811
Preparer Name
K****** L* L*******
Preparer Title
Sr. Compliance Coordinator
Preparer Email
K***********@m*********.com
Preparer Telephone
918-574-7315
Preparer Fax
918-574-7246
Prepared Date
2012-12-19 00:00:00
Authorizer Name
K****** L* L*******
Authorizer Telephone
918-574-7315
Authorizer Title
Sr. Compliance Coordinator
Authorizer Email
K***********@m*********.com
Narrative
At approximately 11:42 october 6, 2011 the scada system in magellan's operations control center indicted a sharp drop in pressure and an increase in flow rate on the #6-10" pipeline between topeka and kansas city. Magellan personnel executed a code red emergency shutdown of the line in accordance with magellan's o&m procedures and notified qualified field personnel to investigate. Subsequent investigation discovered that an excavating contractor had dented the line in several places and punctured it with a tooth of a front end loader while excavating a pond. The excavator did not place a one-call with the kansas one call agency. Magellan personnel immediately began controlling the released product and repaired the line with a segment of new, pretested pipe in accordance with PHMSA regulations and company procedures. The released product was recovered and 4708 cubic yards of effected soil were remediated per company and state requirements.
Report Received Date 2011-11-04 00:00:00
Iyear 2011
Report Number 20110412
Supplemental Number 17121
Report Type Supplemental Final
Operator Id 22610 PHMSA Enforcement
Name Magellan Pipeline Company, Lp
Operator Street Address 100 West 5th Street
Operator City Name Tulsa
Operator State Abbreviation OK
Operator Postal Code 74103
Local Datetime 2011-10-06 11:42:00
Location Latitude 38.98759 Google Maps OpenStreetMap
Location Longitude -95.32997 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls 590
Intentional Release Bbls 0
Recovered Bbls 300
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Cpm Leak Detection System Or Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Calculations)
Incident Identified Datetime 2011-10-06 11:55:00
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Shutdown Due Accident Ind Yes
Shutdown Datetime 2011-10-06 11:46:00
Restart Datetime 2011-10-07 15:12:00
On Site Datetime 2011-10-06 13:30:00
Nrc Rpt Datetime 2011-10-06 12:33:00
Nrc Rpt Num 991799 NRC Report How to search
Ignite Ind No
Explode Ind No
Upstream Valve Type Ind Remotely Controlled
Downstream Valve Type Ind Remotely Controlled
Pipe Fac Name #6-10" Topeka To Kansas City Line
Segment Name Line Segment #6110
Onshore State Abbreviation Ks
Onshore Postal Code 66049
Onshore City Name Lawrence
Onshore County Name Douglas
Designated Location Survey Station No.
Designated Name 6552+02
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 33
Crossing No
Pipe Facility Type Interstate
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 10.75
Pipe Wall Thickness 0.203
Pipe Smys 46000
Pipe Specification Api 5lx-46
Pipe Seam Type Erw - Low Frequency
Pipe Manufacturer Youngstown Steel
Pipe Coating Type Asphalt
Installation Year 1955
Manufactured Year 1955
Material Involved Carbon Steel
Release Type Mechanical Puncture
Puncture Axial 3.5
Puncture Circum 2
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
Usa Drinking Ind Yes
Usa Drinking Yes No Yes
Usa Ecological Ind Yes
Usa Ecological Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 62300
Est Cost Prop Damage 35000
Est Cost Emergency 50000
Est Cost Environmental 520541
Est Cost Other 0
Prpty 667841
Accident Psig 230
Mop Psig 1150
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Length Segment Isolated 262704
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind Yes
Cpm Conf Ind Yes
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The release was the result of a third party line strike by an excavator and did not stem from the operation of the line
Employee Drug Test Ind Yes
Contractor Drug Test Ind No
Num Employees Tested 1
Num Employees Failed 0
Cause Excavation Damage
Cause Details Excavation Damage By Third Party
Ex Party Type Excavation Damage By Third Party
Prior Notification Ind No
Notify Cga Dirt Yes
Private Row Ind Yes
Private Subtype Private Landowner
Pipeline Easement Row Ind Yes
Excavator Type Contractor
Excavator Equipment Backhoe/trackhoe
Work Performed Agriculture
One Call Notified Ind No
Locator Type Unknown/other
Visible Marks No
Service Interruption Yes
Service Interruption Hours 27
Root Cause Category Notification Issue
Root Cause Type No Notification Made To The One-Call Center/811
Preparer Name K****** L* L*******
Preparer Title Sr. Compliance Coordinator
Preparer Email K***********@m*********.com
Preparer Telephone 918-574-7315
Preparer Fax 918-574-7246
Prepared Date 2012-12-19 00:00:00
Authorizer Name K****** L* L*******
Authorizer Telephone 918-574-7315
Authorizer Title Sr. Compliance Coordinator
Authorizer Email K***********@m*********.com
Narrative At approximately 11:42 october 6, 2011 the scada system in magellan's operations control center indicted a sharp drop in pressure and an increase in flow rate on the #6-10" pipeline between topeka and kansas city. Magellan personnel executed a code red emergency shutdown of the line in accordance with magellan's o&m procedures and notified qualified field personnel to investigate. Subsequent investigation discovered that an excavating contractor had dented the line in several places and punctured it with a tooth of a front end loader while excavating a pond. The excavator did not place a one-call with the kansas one call agency. Magellan personnel immediately began controlling the released product and repaired the line with a segment of new, pretested pipe in accordance with PHMSA regulations and company procedures. The released product was recovered and 4708 cubic yards of effected soil were remediated per company and state requirements.

All rights reserved. Copyright © by ClearPHMSA