HL incident on 2011-07-13 — TX

Operator
West Texas Gulf Pipeline Co
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$7,057
Incident datetime
2011-07-13 12:10
Report number
Location
TX
Narrative
Release from tank 42 fill line found during routine station check. Clamp installed until permanent repairs are made. Release due to internal corrosion on dead leg piping. Supplemental information: the contractor injury information previously reported was incorrect. The injury did not occur during the emergency response/cleanup and was irrelevant to this incident. On 11/11/11 all dead leg piping from station including failed section was removed in an effort to mitigate any potential future releases. Additionally, a chemical biocide tank and pump which is activated when the valve to strip off the main line and transfer product to tankage is opened thus treating station piping and tank lines. Re-submitted on 3/19/2013 to include part e5f per PHMSA request.
Detailed record list
Report Received Date
2011-08-12 00:00:00
Iyear
2011
Report Number
20110289
Supplemental Number
18734
Report Type
Supplemental Final
Operator Id
Name
West Texas Gulf Pipeline Co
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2011-07-13 12:10:00
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
70
Intentional Release Bbls
0
Recovered Bbls
60
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2011-07-13 12:10:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2011-07-13 12:10:00
Restart Datetime
2011-07-13 16:00:00
On Site Datetime
2011-07-13 12:30:00
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Wortham Station
Segment Name
Tank 42 Fill Line
Onshore State Abbreviation
Tx
Onshore Postal Code
76693
Onshore City Name
Wortham
Onshore County Name
Freestone
Designated Location
Milepost/valve Station
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
24
Pipe Wall Thickness
0.312
Pipe Smys
24000
Pipe Specification
Unknown
Pipe Seam Type
Erw � Unknown Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Paint
Installation Year
1953
Manufactured Year
1952
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
945
Est Cost Prop Damage
7057
Est Cost Emergency
14183
Est Cost Environmental
5355
Est Cost Other
0
Prpty
27540
Accident Psig
50
Mop Psig
125
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Water Acid Ind
Yes
Int Microbiological Ind
Yes
Int Field Exam Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
No
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
Yes
Exm Handl Ultrasonic Rcnt Year
2011
Exm Handl Ultrasonic Rcnt Ind
Yes
Preparer Name
T*** G* N*******
Preparer Title
Dot Compliance Specialist
Preparer Email
T*********@s**************.com
Preparer Telephone
281-637-6576
Preparer Fax
281-637-6425
Prepared Date
2013-11-15 00:00:00
Authorizer Name
T*** G* N*******
Authorizer Telephone
281-637-6576
Authorizer Title
Dot Compliance Specialist
Authorizer Email
T*********@s**************.com
Narrative
Release from tank 42 fill line found during routine station check. Clamp installed until permanent repairs are made. Release due to internal corrosion on dead leg piping. Supplemental information: the contractor injury information previously reported was incorrect. The injury did not occur during the emergency response/cleanup and was irrelevant to this incident. On 11/11/11 all dead leg piping from station including failed section was removed in an effort to mitigate any potential future releases. Additionally, a chemical biocide tank and pump which is activated when the valve to strip off the main line and transfer product to tankage is opened thus treating station piping and tank lines. Re-submitted on 3/19/2013 to include part e5f per PHMSA request.
Report Received Date 2011-08-12 00:00:00
Iyear 2011
Report Number 20110289
Supplemental Number 18734
Report Type Supplemental Final
Operator Id 22442 PHMSA Enforcement
Name West Texas Gulf Pipeline Co
Operator Street Address 1300 Main Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2011-07-13 12:10:00
Location Latitude 31.7767 Google Maps OpenStreetMap
Location Longitude -98.39635 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 70
Intentional Release Bbls 0
Recovered Bbls 60
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2011-07-13 12:10:00
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Shutdown Due Accident Ind Yes
Shutdown Datetime 2011-07-13 12:10:00
Restart Datetime 2011-07-13 16:00:00
On Site Datetime 2011-07-13 12:30:00
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Wortham Station
Segment Name Tank 42 Fill Line
Onshore State Abbreviation Tx
Onshore Postal Code 76693
Onshore City Name Wortham
Onshore County Name Freestone
Designated Location Milepost/valve Station
Designated Name 0
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 24
Pipe Wall Thickness 0.312
Pipe Smys 24000
Pipe Specification Unknown
Pipe Seam Type Erw � Unknown Frequency
Pipe Manufacturer Unknown
Pipe Coating Type Paint
Installation Year 1953
Manufactured Year 1952
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 945
Est Cost Prop Damage 7057
Est Cost Emergency 14183
Est Cost Environmental 5355
Est Cost Other 0
Prpty 27540
Accident Psig 50
Mop Psig 125
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind No
Cpm In Place Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results Localized Pitting
Int Water Acid Ind Yes
Int Microbiological Ind Yes
Int Field Exam Basis Ind Yes
Int Low Point Pipe Loc Ind Yes
Corrosion Inhibitors No
Corrosion Lining No
Cleaning Dewatering Not Applicable - Not Mainline Pipe
Corrosion Coupons Not Applicable - Not Mainline Pipe
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind Yes
Exm Handl Ultrasonic Rcnt Year 2011
Exm Handl Ultrasonic Rcnt Ind Yes
Preparer Name T*** G* N*******
Preparer Title Dot Compliance Specialist
Preparer Email T*********@s**************.com
Preparer Telephone 281-637-6576
Preparer Fax 281-637-6425
Prepared Date 2013-11-15 00:00:00
Authorizer Name T*** G* N*******
Authorizer Telephone 281-637-6576
Authorizer Title Dot Compliance Specialist
Authorizer Email T*********@s**************.com
Narrative Release from tank 42 fill line found during routine station check. Clamp installed until permanent repairs are made. Release due to internal corrosion on dead leg piping. Supplemental information: the contractor injury information previously reported was incorrect. The injury did not occur during the emergency response/cleanup and was irrelevant to this incident. On 11/11/11 all dead leg piping from station including failed section was removed in an effort to mitigate any potential future releases. Additionally, a chemical biocide tank and pump which is activated when the valve to strip off the main line and transfer product to tankage is opened thus treating station piping and tank lines. Re-submitted on 3/19/2013 to include part e5f per PHMSA request.

All rights reserved. Copyright © by ClearPHMSA