GTG incident on 2011-06-07 — TX

Operator
Tennessee Gas Pipeline Co (El Paso)
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$261,000
Incident datetime
2011-06-07 16:15
Report number
Location
TX
Narrative
Boemre (formerly mms), contacted by black elk energy, notified tgp of a leak offshore in vermillion block 116 that appeared to be in the vicinity of tgp facilities. Tgp mobilized personnel and began to isolate facilities around the leak location. Tgp's 509a-1500 line was found to be the source of the leak. Divers discovered that a 1" body bleed valve and nipple was broken in the nipple threads, possibly caused by outside force impact such as a shrimp net. It should be noted that black elk energy called the nrc about the leak and was assigned no. 978918, which tgp claimed upon contacting the nrc. Tgp was assigned a new nrc number of 978958. The leak was repaired by drilling out the damaged nipple and replacing with a 1-1/4" nippled and valve. The repaired facility was placed back into service.
Detailed record list
Report Received Date
2011-07-05 00:00:00
Iyear
2011
Report Number
20110226
Supplemental Number
15290
Report Type
Original Final
Operator Id
Name
Tennessee Gas Pipeline Co (El Paso)
Operator Street Address
1001 Louisiana St
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2011-06-07 14:42:00
Location Latitude
Location Longitude
Nrc Rpt Num
Nrc Rpt Datetime
2011-06-07 17:53:00
Commodity Released Type
Natural Gas
Unintentional Release
27947
Intentional Release
87646
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2011-06-08 16:00:00
Restart Datetime
2011-06-14 13:00:00
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2011-06-07 16:15:00
On Site Datetime
2011-06-09 17:50:00
On Off Shore
Offshore
Off Water Depth
60
Off Accident Origin
On The Outer Continental Shelf (Ocs)
Off Ocs Area
Vermillion
Off Ocs Block
116
Off Area Accident Type
Below Water, Pipe On Or Above Seabed
Pipe Facility Type
Interstate
System Part Involved
Offshore Pipeline, Including Riser And Riser Bend
Item Involved
Valve
Valve Type
Mainline
Valve Mainline Type
Ball
Valve Manufacturer
Grove
Installation Year
1972
Manufactured Year
1971
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Other
Leak Type Other
Broken 1" Nipple
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
293
Heat Damage Ind
No
Non Heat Damage Ind
No
Hca Fatalities Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
118217
Est Cost Intentional Release
370741
Est Cost Prop Damage
261000
Est Cost Emergency
4000
Est Cost Other
0
Prpty
753958
Accident Psig
806
Mop Psig
1253
Mop Cfr Section
Not On Omb-Approved Form When Submitted
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Length Segment Isolated
384384
Internal Inspection Ind
No
Tight Mitered Ind
Yes
Other Restrictions Ind
Yes
Other Inspection Ind
Yes
Internal Inspection Details
Platform Restrictions And No Launchers Or Receivers Exist To Accommodate An Ili.
Operation Complications Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Other
Accident Details
Producer Black Elk Energy Notified Boemre Who Notified Tgp.
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Operating pressure limits were not exceeded.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Routine Or Normal Fishing Or Other Maritime Activity Not Engaged In Excavation
Outside Force Type
Routine Or Normal Fishing Or Other Maritime Activity Not Engaged In Excavation
Preparer Name
K****** C P*****
Preparer Title
Manager - Dot Compliance Field Support
Preparer Email
K*********@e*****.com
Preparer Telephone
2053257554
Preparer Fax
2053253729
Authorizer Name
K****** C P*****
Authorizer Title
Manager - Dot Compliance Field Support
Authorizer Telephone
2053257554
Authorizer Email
K*********@e*****.com
Narrative
Boemre (formerly mms), contacted by black elk energy, notified tgp of a leak offshore in vermillion block 116 that appeared to be in the vicinity of tgp facilities. Tgp mobilized personnel and began to isolate facilities around the leak location. Tgp's 509a-1500 line was found to be the source of the leak. Divers discovered that a 1" body bleed valve and nipple was broken in the nipple threads, possibly caused by outside force impact such as a shrimp net. It should be noted that black elk energy called the nrc about the leak and was assigned no. 978918, which tgp claimed upon contacting the nrc. Tgp was assigned a new nrc number of 978958. The leak was repaired by drilling out the damaged nipple and replacing with a 1-1/4" nippled and valve. The repaired facility was placed back into service.
Report Received Date 2011-07-05 00:00:00
Iyear 2011
Report Number 20110226
Supplemental Number 15290
Report Type Original Final
Operator Id 19160 PHMSA Enforcement
Name Tennessee Gas Pipeline Co (El Paso)
Operator Street Address 1001 Louisiana St
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2011-06-07 14:42:00
Location Latitude 29.097112 Google Maps OpenStreetMap
Location Longitude -92.349969 Google Maps OpenStreetMap
Nrc Rpt Num 978958 NRC Report How to search
Nrc Rpt Datetime 2011-06-07 17:53:00
Commodity Released Type Natural Gas
Unintentional Release 27947
Intentional Release 87646
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Shutdown Due Accident Ind Yes
Shutdown Datetime 2011-06-08 16:00:00
Restart Datetime 2011-06-14 13:00:00
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Incident Identified Datetime 2011-06-07 16:15:00
On Site Datetime 2011-06-09 17:50:00
On Off Shore Offshore
Off Water Depth 60
Off Accident Origin On The Outer Continental Shelf (Ocs)
Off Ocs Area Vermillion
Off Ocs Block 116
Off Area Accident Type Below Water, Pipe On Or Above Seabed
Pipe Facility Type Interstate
System Part Involved Offshore Pipeline, Including Riser And Riser Bend
Item Involved Valve
Valve Type Mainline
Valve Mainline Type Ball
Valve Manufacturer Grove
Installation Year 1972
Manufactured Year 1971
Material Involved Carbon Steel
Release Type Leak
Leak Type Other
Leak Type Other Broken 1" Nipple
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 293
Heat Damage Ind No
Non Heat Damage Ind No
Hca Fatalities Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 118217
Est Cost Intentional Release 370741
Est Cost Prop Damage 261000
Est Cost Emergency 4000
Est Cost Other 0
Prpty 753958
Accident Psig 806
Mop Psig 1253
Mop Cfr Section Not On Omb-Approved Form When Submitted View CFR 49 §192
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Manual
Length Segment Isolated 384384
Internal Inspection Ind No
Tight Mitered Ind Yes
Other Restrictions Ind Yes
Other Inspection Ind Yes
Internal Inspection Details Platform Restrictions And No Launchers Or Receivers Exist To Accommodate An Ili.
Operation Complications Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Other
Accident Details Producer Black Elk Energy Notified Boemre Who Notified Tgp.
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Operating pressure limits were not exceeded.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Outside Force Damage
Cause Details Routine Or Normal Fishing Or Other Maritime Activity Not Engaged In Excavation
Outside Force Type Routine Or Normal Fishing Or Other Maritime Activity Not Engaged In Excavation
Preparer Name K****** C P*****
Preparer Title Manager - Dot Compliance Field Support
Preparer Email K*********@e*****.com
Preparer Telephone 2053257554
Preparer Fax 2053253729
Authorizer Name K****** C P*****
Authorizer Title Manager - Dot Compliance Field Support
Authorizer Telephone 2053257554
Authorizer Email K*********@e*****.com
Narrative Boemre (formerly mms), contacted by black elk energy, notified tgp of a leak offshore in vermillion block 116 that appeared to be in the vicinity of tgp facilities. Tgp mobilized personnel and began to isolate facilities around the leak location. Tgp's 509a-1500 line was found to be the source of the leak. Divers discovered that a 1" body bleed valve and nipple was broken in the nipple threads, possibly caused by outside force impact such as a shrimp net. It should be noted that black elk energy called the nrc about the leak and was assigned no. 978918, which tgp claimed upon contacting the nrc. Tgp was assigned a new nrc number of 978958. The leak was repaired by drilling out the damaged nipple and replacing with a 1-1/4" nippled and valve. The repaired facility was placed back into service.