GD incident on 2011-06-06 — NY

Operator
Consolidated Edison Co Of New York
Cause
Incorrect Operation
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$0
Incident datetime
2011-06-06 13:13
Report number
Location
NY, NEW YORK
Narrative
*********************this is not a DOT reportable incident----this report is for information only************************ a con edison construction inspector reported a contractor damaged at 533 e 11 st., manhattan, new york to the gas emergency response center (gerc). A multiple resource response event (code murre) was initiated and the gerc dispatched the fire department of the city of ny (fdny), gas distribution services (gds), construction and supervision. Gds responded and at 13:22 hrs. Reported receiving a 4% gas reading in the atmosphere of the basement. The fdny evacuated 12 residents of this 7 story building at 13:25 hrs., gds reported that sicon electrical contractors working for con edison construction management cut through a 3" steel pipe 5 feet from the outside foundation wall, the pipe contained a 1 1/4" low pressure copper gas service. Additional gds mechanics responded to location and together they were able to secure the damaged 1 1/4" copper service in the 3" sleeve at 14:30 hrs. The fdny vented the basement and the evacuation ended at 14:42 hrs. A gds mechanic was offered oxygen by the fd after securing the leak, the fdny administered the oxygen and he was later evaluated by ems on scene and returned to work at 15:41 hrs. Fdny, nyc oem, nyc dep hazmat and the new york times were on location. The nys psc, nyc dep and US DOT were all notified. This was an upgraded level incident. *********************this is not a DOT reportable incident----this report is for information only************************
Detailed record list
Occurred At
2011-06-06 13:13:00
Year
2011
Report Received Date
2011-06-28 00:00:00
Iyear
2011.0
Report Number
20110207.0
Supplemental Number
15382.0
Report Type
Supplemental Final
Operator Id
Name
Consolidated Edison Co Of New York
Operator Street Address
4 Irving Place
Operator City Name
New York
Operator State Abbreviation
NY
Operator Postal Code
10003
Local Datetime
2011-06-06 13:13:00
Location Street Address
533 East 11 Street
Location City Name
New York
Location County Name
New York
Location State Abbreviation
NY
Location Postal Code
10009-4653
Location Latitude
Location Longitude
Nrc Rpt Datetime
2011-06-06 14:58:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
15.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
12.0
Incident Identified Datetime
2011-06-06 13:13:00
On Site Datetime
2011-06-06 13:22:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Depth Of Cover
30.0
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Service
Installation Year
1978.0
Pipe Diameter
1.25
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Copper
Release Type
Mechanical Puncture
Class Location Type
Class 4 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
0.0
Est Cost Emergency
1180.0
Est Cost Other
0.0
Est Cost Unintentional Release
45.0
Prpty
1225.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
1.0
Accident Psig
0.25
Normal Psig
0.25
Mop Psig
0.5
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage
Operation Type
Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage
Related Other Ind
Yes
Operation Related Details
Contractor Working For Electric Operations Incorrectly Identified 3" Steel Gas Sleeve (With Gas Service Inside Sleeve) For A 3" Electric Conduit Sleeve
Category Type
Other Maintenance
Operator Qualification Ind
No
Preparer Name
K**** F****
Preparer Title
Operations Manager-Gas Emergency Response Center
Preparer Email
F*****@c****.com
Preparer Telephone
718-319-2310
Preparer Fax
718-904-4607
Authorizer Name
V***** D******
Authorizer Title
Dept. Manager-Gas Emergency Response Center
Authorizer Telephone
718-319-2350
Authorizer Email
D*******@c****.com
Narrative
*********************this is not a DOT reportable incident----this report is for information only************************ a con edison construction inspector reported a contractor damaged at 533 e 11 st., manhattan, new york to the gas emergency response center (gerc). A multiple resource response event (code murre) was initiated and the gerc dispatched the fire department of the city of ny (fdny), gas distribution services (gds), construction and supervision. Gds responded and at 13:22 hrs. Reported receiving a 4% gas reading in the atmosphere of the basement. The fdny evacuated 12 residents of this 7 story building at 13:25 hrs., gds reported that sicon electrical contractors working for con edison construction management cut through a 3" steel pipe 5 feet from the outside foundation wall, the pipe contained a 1 1/4" low pressure copper gas service. Additional gds mechanics responded to location and together they were able to secure the damaged 1 1/4" copper service in the 3" sleeve at 14:30 hrs. The fdny vented the basement and the evacuation ended at 14:42 hrs. A gds mechanic was offered oxygen by the fd after securing the leak, the fdny administered the oxygen and he was later evaluated by ems on scene and returned to work at 15:41 hrs. Fdny, nyc oem, nyc dep hazmat and the new york times were on location. The nys psc, nyc dep and US DOT were all notified. This was an upgraded level incident. *********************this is not a DOT reportable incident----this report is for information only************************
Occurred At 2011-06-06 13:13:00
Year 2011
Report Received Date 2011-06-28 00:00:00
Iyear 2011.0
Report Number 20110207.0
Supplemental Number 15382.0
Report Type Supplemental Final
Operator Id 2704 PHMSA Enforcement
Name Consolidated Edison Co Of New York
Operator Street Address 4 Irving Place
Operator City Name New York
Operator State Abbreviation NY
Operator Postal Code 10003
Local Datetime 2011-06-06 13:13:00
Location Street Address 533 East 11 Street
Location City Name New York
Location County Name New York
Location State Abbreviation NY
Location Postal Code 10009-4653
Location Latitude 40.728042 Google Maps OpenStreetMap
Location Longitude -73.980236 Google Maps OpenStreetMap
Nrc Rpt Datetime 2011-06-06 14:58:00
Nrc Rpt Num 978815 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 15.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind No
Explode Ind No
Num Pub Evacuated 12.0
Incident Identified Datetime 2011-06-06 13:13:00
On Site Datetime 2011-06-06 13:22:00
Federal No
Location Type Public Property
Incident Area Type Underground
Incident Area Subtype Exposed Due To Excavation
Depth Of Cover 30.0
Crossing No
Pipe Facility Type Privately Owned
System Part Involved Service
Installation Year 1978.0
Pipe Diameter 1.25
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Copper
Release Type Mechanical Puncture
Class Location Type Class 4 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 0.0
Est Cost Emergency 1180.0
Est Cost Other 0.0
Est Cost Unintentional Release 45.0
Prpty 1225.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 1.0
Accident Psig 0.25
Normal Psig 0.25
Mop Psig 0.5
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Incorrect Operation
Cause Details Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage
Operation Type Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage
Related Other Ind Yes
Operation Related Details Contractor Working For Electric Operations Incorrectly Identified 3" Steel Gas Sleeve (With Gas Service Inside Sleeve) For A 3" Electric Conduit Sleeve
Category Type Other Maintenance
Operator Qualification Ind No
Preparer Name K**** F****
Preparer Title Operations Manager-Gas Emergency Response Center
Preparer Email F*****@c****.com
Preparer Telephone 718-319-2310
Preparer Fax 718-904-4607
Authorizer Name V***** D******
Authorizer Title Dept. Manager-Gas Emergency Response Center
Authorizer Telephone 718-319-2350
Authorizer Email D*******@c****.com
Narrative *********************this is not a DOT reportable incident----this report is for information only************************ a con edison construction inspector reported a contractor damaged at 533 e 11 st., manhattan, new york to the gas emergency response center (gerc). A multiple resource response event (code murre) was initiated and the gerc dispatched the fire department of the city of ny (fdny), gas distribution services (gds), construction and supervision. Gds responded and at 13:22 hrs. Reported receiving a 4% gas reading in the atmosphere of the basement. The fdny evacuated 12 residents of this 7 story building at 13:25 hrs., gds reported that sicon electrical contractors working for con edison construction management cut through a 3" steel pipe 5 feet from the outside foundation wall, the pipe contained a 1 1/4" low pressure copper gas service. Additional gds mechanics responded to location and together they were able to secure the damaged 1 1/4" copper service in the 3" sleeve at 14:30 hrs. The fdny vented the basement and the evacuation ended at 14:42 hrs. A gds mechanic was offered oxygen by the fd after securing the leak, the fdny administered the oxygen and he was later evaluated by ems on scene and returned to work at 15:41 hrs. Fdny, nyc oem, nyc dep hazmat and the new york times were on location. The nys psc, nyc dep and US DOT were all notified. This was an upgraded level incident. *********************this is not a DOT reportable incident----this report is for information only************************

All rights reserved. Copyright © by ClearPHMSA