GTG incident on 2011-05-29 — TX

Operator
Panhandle Eastern Pipeline Co
Cause
Corrosion Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$20,000
Incident datetime
2011-05-29 08:07
Report number
Location
TX
Narrative
At 8:07 am on may 29, 2011, panhandle eastern pipe line company received a call from a retired employee reporting blowing gas at the borchers storage field. A pepl employee was at the field and isolated the affected line segment within 23 minutes. Visual observation of the failed pipe segment indicates internal wall loss due to corrosion for 5 feet in the vicinity of the fracture immediately downstream of a 4" to 6" reducer, in a low point of the pipe. Laboratory analysis of the failed pipe segment concluded that the internal corrosion was likely the result of aqueous corrosion caused by water and other contaminants in the product stream. It is also likely that under deposit corrosion created the local environment that resulted in the corrosion observed. The corrosion deposits were not consistent with microbiological-assisted corrosion, and the corrosion was not associated with the erw seam. **this report is being submitted in response to PHMSA's request for supplemental reports from operators who submitted reports for incidents occurring after january 1, 2010, with any of the following: (1) ``pipe girth weld'' was selected as the ``item involved in incident'' in part c3 of the report. The revised report collects data about the pipe adjacent to the girth weld. (2) ``function of pipeline system'' is null in part e5f of the report. The revised report collects the function of the pipeline system for all incidents. This report has no further updates and is being submitted as a final.
Detailed record list
Report Received Date
2011-06-23 00:00:00
Iyear
2011
Report Number
20110194
Supplemental Number
16024
Report Type
Supplemental Final
Operator Id
Name
Panhandle Eastern Pipeline Co
Operator Street Address
5051 Westheimer Road
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77056
Local Datetime
2011-05-29 08:07:00
Location Latitude
Location Longitude
Nrc Rpt Num
Nrc Rpt Datetime
2011-05-29 13:06:00
Commodity Released Type
Natural Gas
Unintentional Release
45000
Intentional Release
1750
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2011-05-29 08:30:00
Still Shutdown Ind
Yes
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2011-05-29 08:07:00
On Site Datetime
2011-05-29 08:07:00
On Off Shore
Onshore
Onshore State Abbreviation
Ks
Onshore Postal Code
67864
Onshore City Name
Meade
Onshore County Name
Meade
Pipe Fac Name
Borchers Storage Field
Segment Name
Lowen 1-10/35-03-034-08
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
72
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
6.625
Pipe Wall Thickness
0.219
Pipe Smys
46000
Pipe Specification
5l
Pipe Seam Type
Longitudinal Erw - High Frequency
Pipe Manufacturer
Tex-Tube
Pipe Coating Type
Field Applied Epoxy
Installation Year
1981
Manufactured Year
1981
Material Involved
Carbon Steel
Release Type
Rupture
Rupture Orient
Longitudinal
Rupture Length
90
Rupture Width
14
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
198
Heat Damage Ind
No
Non Heat Damage Ind
No
Hca Fatalities Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
180000
Est Cost Intentional Release
7000
Est Cost Prop Damage
20000
Est Cost Emergency
1000
Est Cost Other
0
Prpty
208000
Accident Psig
1639
Mop Psig
1875
Mop Cfr Section
Not On Omb-Approved Form When Submitted
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Length Segment Isolated
3039
Internal Inspection Ind
No
Diameter Change Ind
Yes
Operation Complications Ind
No
Pipeline Function
Transmission In Storage Field
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Public
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
2
Num Employees Failed
0
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
General Corrosion
Int Water Acid Ind
Yes
Int Field Exam Basis Ind
Yes
Int Metallurgical Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
Yes
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
N***** H******
Preparer Title
Director Interstate Regulatory Compliance
Preparer Email
N*************@e*************.com
Preparer Telephone
713-857-5479
Authorizer Name
N***** H******
Authorizer Title
Director Interstate Regulatory Compliance
Authorizer Telephone
713-857-5479
Authorizer Email
N*************@e*************.com
Narrative
At 8:07 am on may 29, 2011, panhandle eastern pipe line company received a call from a retired employee reporting blowing gas at the borchers storage field. A pepl employee was at the field and isolated the affected line segment within 23 minutes. Visual observation of the failed pipe segment indicates internal wall loss due to corrosion for 5 feet in the vicinity of the fracture immediately downstream of a 4" to 6" reducer, in a low point of the pipe. Laboratory analysis of the failed pipe segment concluded that the internal corrosion was likely the result of aqueous corrosion caused by water and other contaminants in the product stream. It is also likely that under deposit corrosion created the local environment that resulted in the corrosion observed. The corrosion deposits were not consistent with microbiological-assisted corrosion, and the corrosion was not associated with the erw seam. **this report is being submitted in response to PHMSA's request for supplemental reports from operators who submitted reports for incidents occurring after january 1, 2010, with any of the following: (1) ``pipe girth weld'' was selected as the ``item involved in incident'' in part c3 of the report. The revised report collects data about the pipe adjacent to the girth weld. (2) ``function of pipeline system'' is null in part e5f of the report. The revised report collects the function of the pipeline system for all incidents. This report has no further updates and is being submitted as a final.
Report Received Date 2011-06-23 00:00:00
Iyear 2011
Report Number 20110194
Supplemental Number 16024
Report Type Supplemental Final
Operator Id 15105 PHMSA Enforcement
Name Panhandle Eastern Pipeline Co
Operator Street Address 5051 Westheimer Road
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77056
Local Datetime 2011-05-29 08:07:00
Location Latitude 37.212617 Google Maps OpenStreetMap
Location Longitude -100.355841 Google Maps OpenStreetMap
Nrc Rpt Num 977716 NRC Report How to search
Nrc Rpt Datetime 2011-05-29 13:06:00
Commodity Released Type Natural Gas
Unintentional Release 45000
Intentional Release 1750
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Shutdown Due Accident Ind Yes
Shutdown Datetime 2011-05-29 08:30:00
Still Shutdown Ind Yes
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Incident Identified Datetime 2011-05-29 08:07:00
On Site Datetime 2011-05-29 08:07:00
On Off Shore Onshore
Onshore State Abbreviation Ks
Onshore Postal Code 67864
Onshore City Name Meade
Onshore County Name Meade
Pipe Fac Name Borchers Storage Field
Segment Name Lowen 1-10/35-03-034-08
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 72
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Pipeline, Including Valve Sites
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 6.625
Pipe Wall Thickness 0.219
Pipe Smys 46000
Pipe Specification 5l
Pipe Seam Type Longitudinal Erw - High Frequency
Pipe Manufacturer Tex-Tube
Pipe Coating Type Field Applied Epoxy
Installation Year 1981
Manufactured Year 1981
Material Involved Carbon Steel
Release Type Rupture
Rupture Orient Longitudinal
Rupture Length 90
Rupture Width 14
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 198
Heat Damage Ind No
Non Heat Damage Ind No
Hca Fatalities Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 180000
Est Cost Intentional Release 7000
Est Cost Prop Damage 20000
Est Cost Emergency 1000
Est Cost Other 0
Prpty 208000
Accident Psig 1639
Mop Psig 1875
Mop Cfr Section Not On Omb-Approved Form When Submitted View CFR 49 §192
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Manual
Length Segment Isolated 3039
Internal Inspection Ind No
Diameter Change Ind Yes
Operation Complications Ind No
Pipeline Function Transmission In Storage Field
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Notification From Public
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind Yes
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind Yes
Contractor Drug Test Ind No
Num Employees Tested 2
Num Employees Failed 0
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results General Corrosion
Int Water Acid Ind Yes
Int Field Exam Basis Ind Yes
Int Metallurgical Basis Ind Yes
Int Low Point Pipe Loc Ind Yes
Corrosion Inhibitors Yes
Corrosion Lining No
Cleaning Dewatering Not Applicable - Not Mainline Pipe
Corrosion Coupons Not Applicable - Not Mainline Pipe
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name N***** H******
Preparer Title Director Interstate Regulatory Compliance
Preparer Email N*************@e*************.com
Preparer Telephone 713-857-5479
Authorizer Name N***** H******
Authorizer Title Director Interstate Regulatory Compliance
Authorizer Telephone 713-857-5479
Authorizer Email N*************@e*************.com
Narrative At 8:07 am on may 29, 2011, panhandle eastern pipe line company received a call from a retired employee reporting blowing gas at the borchers storage field. A pepl employee was at the field and isolated the affected line segment within 23 minutes. Visual observation of the failed pipe segment indicates internal wall loss due to corrosion for 5 feet in the vicinity of the fracture immediately downstream of a 4" to 6" reducer, in a low point of the pipe. Laboratory analysis of the failed pipe segment concluded that the internal corrosion was likely the result of aqueous corrosion caused by water and other contaminants in the product stream. It is also likely that under deposit corrosion created the local environment that resulted in the corrosion observed. The corrosion deposits were not consistent with microbiological-assisted corrosion, and the corrosion was not associated with the erw seam. **this report is being submitted in response to PHMSA's request for supplemental reports from operators who submitted reports for incidents occurring after january 1, 2010, with any of the following: (1) ``pipe girth weld'' was selected as the ``item involved in incident'' in part c3 of the report. The revised report collects data about the pipe adjacent to the girth weld. (2) ``function of pipeline system'' is null in part e5f of the report. The revised report collects the function of the pipeline system for all incidents. This report has no further updates and is being submitted as a final.