Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2011-02-22 — PA
Operator
Buckeye Partners, Lp
Cause
Natural Force Damage
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2011-02-22 07:01
Report number
Location
PA
Narrative
At 07:01 am on february 22, 2011 a release was identified by buckeye personnel at the argo terminal (betag) during a routine check. The line was isolated and emergency repsonse procedures were initiated. 25 gallons of jet fuel leaked through a 1" ball valve on the prover incoming line. The cause of the release has been determined to be a crack in the 1" ball valve due to water freezing and then splitting the valve. The valve has been replaced and is back in service. All impacted soil and gravel was removed and all remediation is complete. No further action is required. *supplemental section e 5f answered
Detailed record list
Report Received Date
2011-03-23 00:00:00
Iyear
2011
Report Number
20110101
Supplemental Number
18813
Report Type
Supplemental Final
Operator Id
1845
Name
Buckeye Partners, Lp
Operator Street Address
The Buckeye Building 6161 Hamilton Boulevar
Operator City Name
Allentown
Operator State Abbreviation
PA
Operator Postal Code
18106
Local Datetime
2011-02-22 07:01:00
Location Latitude
41.7643
Location Longitude
-87.8361
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
0.6
Intentional Release Bbls
0
Recovered Bbls
0.6
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Incident Identified Datetime
2011-02-22 07:01:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
All Valves Were Closed And Loto To Isolate The Section.
On Site Datetime
2011-02-22 07:01:00
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Argo Terminal
Segment Name
Betag
Onshore State Abbreviation
Il
Onshore Postal Code
60501
Onshore City Name
Bedford Park
Onshore County Name
Cook
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Pipe Facility Type
Interstate
Item Involved
Valve
Valve Type
Auxiliary Or Other Valve
Release Type
Leak
Leak Type
Crack
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
0
Est Cost Emergency
6175
Est Cost Environmental
3360
Est Cost Other
0
Prpty
9535
Pipeline Function
> 20% Smys Regulated Transmission
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Natural Force Damage
Cause Details
Temperature
Natural Force Type
Temperature
Nf Extreme Weather Ind
No
Preparer Name
B*** Y**********
Preparer Title
Compliance Specialist
Preparer Email
B***********@b******.com
Preparer Telephone
610-904-4958
Preparer Fax
610-904-4545
Prepared Date
2013-12-10 00:00:00
Authorizer Name
J*** R*******
Authorizer Telephone
610-904-4185
Authorizer Title
Regulatory Compliance Group Leader
Authorizer Email
J********@b******.com
Narrative
At 07:01 am on february 22, 2011 a release was identified by buckeye personnel at the argo terminal (betag) during a routine check. The line was isolated and emergency repsonse procedures were initiated. 25 gallons of jet fuel leaked through a 1" ball valve on the prover incoming line. The cause of the release has been determined to be a crack in the 1" ball valve due to water freezing and then splitting the valve. The valve has been replaced and is back in service. All impacted soil and gravel was removed and all remediation is complete. No further action is required. *supplemental section e 5f answered
| Report Received Date | 2011-03-23 00:00:00 |
|---|---|
| Iyear | 2011 |
| Report Number | 20110101 |
| Supplemental Number | 18813 |
| Report Type | Supplemental Final |
| Operator Id | 1845 PHMSA Enforcement |
| Name | Buckeye Partners, Lp |
| Operator Street Address | The Buckeye Building 6161 Hamilton Boulevar |
| Operator City Name | Allentown |
| Operator State Abbreviation | PA |
| Operator Postal Code | 18106 |
| Local Datetime | 2011-02-22 07:01:00 |
| Location Latitude | 41.7643 Google Maps OpenStreetMap |
| Location Longitude | -87.8361 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Diesel, Fuel Oil, Kerosene, Jet Fuel |
| Unintentional Release Bbls | 0.6 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0.6 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Incident Identified Datetime | 2011-02-22 07:01:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | All Valves Were Closed And Loto To Isolate The Section. |
| On Site Datetime | 2011-02-22 07:01:00 |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Argo Terminal |
| Segment Name | Betag |
| Onshore State Abbreviation | Il |
| Onshore Postal Code | 60501 |
| Onshore City Name | Bedford Park |
| Onshore County Name | Cook |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Pipe Facility Type | Interstate |
| Item Involved | Valve |
| Valve Type | Auxiliary Or Other Valve |
| Release Type | Leak |
| Leak Type | Crack |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 0 |
| Est Cost Emergency | 6175 |
| Est Cost Environmental | 3360 |
| Est Cost Other | 0 |
| Prpty | 9535 |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Natural Force Damage |
| Cause Details | Temperature |
| Natural Force Type | Temperature |
| Nf Extreme Weather Ind | No |
| Preparer Name | B*** Y********** |
| Preparer Title | Compliance Specialist |
| Preparer Email | B***********@b******.com |
| Preparer Telephone | 610-904-4958 |
| Preparer Fax | 610-904-4545 |
| Prepared Date | 2013-12-10 00:00:00 |
| Authorizer Name | J*** R******* |
| Authorizer Telephone | 610-904-4185 |
| Authorizer Title | Regulatory Compliance Group Leader |
| Authorizer Email | J********@b******.com |
| Narrative | At 07:01 am on february 22, 2011 a release was identified by buckeye personnel at the argo terminal (betag) during a routine check. The line was isolated and emergency repsonse procedures were initiated. 25 gallons of jet fuel leaked through a 1" ball valve on the prover incoming line. The cause of the release has been determined to be a crack in the 1" ball valve due to water freezing and then splitting the valve. The valve has been replaced and is back in service. All impacted soil and gravel was removed and all remediation is complete. No further action is required. *supplemental section e 5f answered |