GD incident on 2011-01-18 — NY
Operator
Consolidated Edison Co Of New York
Cause
Corrosion Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2011-01-18 15:56
Report number
Location
NY, BRONX
Narrative
This is not DOT reportable! This report is for record purposes only. On january 18, 2011 the new york fire department (fdny) reported a building fire and a high co condition at 60 knolls crescent, bronx, new york to the gas emergency response center (gerc). Gas distribution services (gds) responded and reported that there was a con edison electric emergency responder on location. Gds investigated and reported that there was an active gas fed fire outside the building in the grass area where the customer-owned gas and electric services cross (inside the property line). Gds and the fdny located and shut the curb valve on the service at 16:09 and the fire was extinguished. Cooking gas supplying 120 apartments was interrupted but the gas boiler was not affected as it is supplied from a separate service. At 18:17 the electric service to building was cut and the electric related evacuation ended. Gds reported that the fire appeared to have been where the customer-owned electric cable crossed over the customer-owned 4" low pressure steel gas service (inside the property line). Bronx gas construction excavated over the main and cut the gas service off for safety. On january 19, 2011 a new service to the building was installed and service was restored. There was less than $50,000.00 in damages (small patch of grass only) and upon consultation with usdot representative wayne chan, this is not DOT reportable. There were no injuries and this is an upgraded level incident.
Detailed record list
Occurred At
2011-01-18 15:56:00
Year
2011
Report Received Date
2011-02-01 00:00:00
Iyear
2011.0
Report Number
20110017.0
Supplemental Number
15179.0
Report Type
Original Final
Operator Id
2704
Name
Consolidated Edison Co Of New York
Operator Street Address
4 Irving Place
Operator City Name
New York
Operator State Abbreviation
NY
Operator Postal Code
10003
Local Datetime
2011-01-18 15:07:00
Location Street Address
60 Knolls Crescent
Location City Name
New York
Location County Name
Bronx
Location State Abbreviation
NY
Location Postal Code
10463-6319
Location Latitude
40.879437
Location Longitude
-73.917542
Nrc Rpt Datetime
2011-01-18 16:08:00
Nrc Rpt Num
965040
Commodity Released Type
Natural Gas
Unintentional Release
0.15
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2011-01-18 15:56:00
On Site Datetime
2011-01-18 15:56:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
36.0
Crossing
No
Pipe Facility Type
Other
Pipe Type Other
Customer-Owned Piping
System Part Involved
Service
Installation Year
1951.0
Pipe Diameter
4.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 4 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
0.0
Est Cost Emergency
500.0
Est Cost Other
5683.0
Est Cost Other Details
Construction Repairs
Est Cost Unintentional Release
10.0
Prpty
6193.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
1.0
Accident Psig
0.25
Normal Psig
0.25
Mop Psig
0.5
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Galvanic Corrosion Ind
Yes
Field Exam Basis Ind
Yes
Underground Location
Yes
Under Cathodic Protection Ind
No
Shielding Evident
No
Cathodic Survey Type
No
Prior Damage
No
Coating Type
None
Cor Hydrotest Conducted Ind
No
Preparer Name
K**** F****
Preparer Title
Manager--Gas Emergency Response Center
Preparer Email
F*****@c****.com
Preparer Telephone
718-319-2310
Preparer Fax
718-904-4607
Authorizer Name
V***** D******
Authorizer Title
Dept. Manager--Gas Emergency Response Center
Authorizer Telephone
718-319-2350
Authorizer Email
D*******@c****.com
Narrative
This is not DOT reportable! This report is for record purposes only. On january 18, 2011 the new york fire department (fdny) reported a building fire and a high co condition at 60 knolls crescent, bronx, new york to the gas emergency response center (gerc). Gas distribution services (gds) responded and reported that there was a con edison electric emergency responder on location. Gds investigated and reported that there was an active gas fed fire outside the building in the grass area where the customer-owned gas and electric services cross (inside the property line). Gds and the fdny located and shut the curb valve on the service at 16:09 and the fire was extinguished. Cooking gas supplying 120 apartments was interrupted but the gas boiler was not affected as it is supplied from a separate service. At 18:17 the electric service to building was cut and the electric related evacuation ended. Gds reported that the fire appeared to have been where the customer-owned electric cable crossed over the customer-owned 4" low pressure steel gas service (inside the property line). Bronx gas construction excavated over the main and cut the gas service off for safety. On january 19, 2011 a new service to the building was installed and service was restored. There was less than $50,000.00 in damages (small patch of grass only) and upon consultation with usdot representative wayne chan, this is not DOT reportable. There were no injuries and this is an upgraded level incident.
| Occurred At | 2011-01-18 15:56:00 |
|---|---|
| Year | 2011 |
| Report Received Date | 2011-02-01 00:00:00 |
| Iyear | 2011.0 |
| Report Number | 20110017.0 |
| Supplemental Number | 15179.0 |
| Report Type | Original Final |
| Operator Id | 2704 PHMSA Enforcement |
| Name | Consolidated Edison Co Of New York |
| Operator Street Address | 4 Irving Place |
| Operator City Name | New York |
| Operator State Abbreviation | NY |
| Operator Postal Code | 10003 |
| Local Datetime | 2011-01-18 15:07:00 |
| Location Street Address | 60 Knolls Crescent |
| Location City Name | New York |
| Location County Name | Bronx |
| Location State Abbreviation | NY |
| Location Postal Code | 10463-6319 |
| Location Latitude | 40.879437 Google Maps OpenStreetMap |
| Location Longitude | -73.917542 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2011-01-18 16:08:00 |
| Nrc Rpt Num | 965040 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 0.15 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2011-01-18 15:56:00 |
| On Site Datetime | 2011-01-18 15:56:00 |
| Federal | No |
| Location Type | Private Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 36.0 |
| Crossing | No |
| Pipe Facility Type | Other |
| Pipe Type Other | Customer-Owned Piping |
| System Part Involved | Service |
| Installation Year | 1951.0 |
| Pipe Diameter | 4.0 |
| Pipe Specification | Unknown |
| Pipe Manufacturer | Unknown |
| Material Involved | Steel |
| Steel Seam Type | Other |
| Steel Seam Type Details | Unknown |
| Release Type | Leak |
| Leak Type | Pinhole |
| Class Location Type | Class 4 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 0.0 |
| Est Cost Emergency | 500.0 |
| Est Cost Other | 5683.0 |
| Est Cost Other Details | Construction Repairs |
| Est Cost Unintentional Release | 10.0 |
| Prpty | 6193.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 1.0 |
| Accident Psig | 0.25 |
| Normal Psig | 0.25 |
| Mop Psig | 0.5 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Emergency Responder |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | External Corrosion |
| Internal External | External Corrosion |
| Visual Exam Results | Localized Pitting |
| Galvanic Corrosion Ind | Yes |
| Field Exam Basis Ind | Yes |
| Underground Location | Yes |
| Under Cathodic Protection Ind | No |
| Shielding Evident | No |
| Cathodic Survey Type | No |
| Prior Damage | No |
| Coating Type | None |
| Cor Hydrotest Conducted Ind | No |
| Preparer Name | K**** F**** |
| Preparer Title | Manager--Gas Emergency Response Center |
| Preparer Email | F*****@c****.com |
| Preparer Telephone | 718-319-2310 |
| Preparer Fax | 718-904-4607 |
| Authorizer Name | V***** D****** |
| Authorizer Title | Dept. Manager--Gas Emergency Response Center |
| Authorizer Telephone | 718-319-2350 |
| Authorizer Email | D*******@c****.com |
| Narrative | This is not DOT reportable! This report is for record purposes only. On january 18, 2011 the new york fire department (fdny) reported a building fire and a high co condition at 60 knolls crescent, bronx, new york to the gas emergency response center (gerc). Gas distribution services (gds) responded and reported that there was a con edison electric emergency responder on location. Gds investigated and reported that there was an active gas fed fire outside the building in the grass area where the customer-owned gas and electric services cross (inside the property line). Gds and the fdny located and shut the curb valve on the service at 16:09 and the fire was extinguished. Cooking gas supplying 120 apartments was interrupted but the gas boiler was not affected as it is supplied from a separate service. At 18:17 the electric service to building was cut and the electric related evacuation ended. Gds reported that the fire appeared to have been where the customer-owned electric cable crossed over the customer-owned 4" low pressure steel gas service (inside the property line). Bronx gas construction excavated over the main and cut the gas service off for safety. On january 19, 2011 a new service to the building was installed and service was restored. There was less than $50,000.00 in damages (small patch of grass only) and upon consultation with usdot representative wayne chan, this is not DOT reportable. There were no injuries and this is an upgraded level incident. |