HL incident on 2010-11-01 — OK

Operator
Oneok Ngl Pipeline Lp
Cause
Corrosion Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$244,000
Incident datetime
2010-11-01 14:55
Report number
Location
OK
Narrative
Third party observed product vapors on pipeline right of way and called emergency number found on nearby pipeline right of way marker sign. Pipeline control center shutdown pipeline and dispatched company field personnel to release site. Company personnel verified release to be on oneok right of way at which time the segment of pipeline was isolated. Product in pipeline was displaced with nitrogen and a section of pipe was removed and replaced with new pipe. Inspection determined release was caused by microbiological corrosion.
Detailed record list
Report Received Date
2010-11-18 00:00:00
Iyear
2010
Report Number
20100246
Supplemental Number
15612
Report Type
Supplemental Final
Operator Id
Name
Oneok Ngl Pipeline Lp
Operator Street Address
100 West Fifth Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2010-11-01 14:55:00
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
241
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Notification From Public
Incident Identified Datetime
2010-11-01 14:55:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2010-11-01 16:25:00
Restart Datetime
2010-11-06 09:30:00
On Site Datetime
2010-11-01 15:30:00
Nrc Rpt Datetime
2010-11-01 16:35:00
Nrc Rpt Num
Ignite Ind
No
Explode Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
Sterling 1 Index 10177
Segment Name
Sterling 1 Between Valves S1-39 & S1-40
Onshore State Abbreviation
Tx
Onshore Postal Code
75491
Onshore City Name
Whitewright
Onshore County Name
Fannin
Designated Location
Milepost/valve Station
Designated Name
13265+65
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
54
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
8.625
Pipe Wall Thickness
0.188
Pipe Smys
46000
Pipe Specification
0.72
Pipe Seam Type
Erw - High Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Extruded Polyehylene
Installation Year
1981
Manufactured Year
1981
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
6358
Est Cost Prop Damage
244000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
250358
Accident Psig
1042
Mop Psig
1335
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
84480
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
Yes
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Microbiological Corrosion Ind
Yes
Field Exam Basis Ind
Yes
Other Basis Ind
Yes
Corrosion Basis Details
Visual Third Party Metallurgical Analysis Specialist
Underground Location
Yes
Under Cathodic Protection Ind
Yes
Cathodic Pro Start Year
1981
Shielding Evident
Yes
Cathodic Survey Type
Yes
Cp Annual Survey Ind
Yes
Cp Annual Survey Year
2010
Prior Damage
Yes
Collected Data Ind
Yes
Other Recent Year
2007
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
P**** G**********
Preparer Email
P****************@o****.com
Preparer Telephone
580-395-6238
Preparer Fax
580-395-2933
Prepared Date
2011-02-10 00:00:00
Authorizer Name
N*** J****
Authorizer Telephone
580-395-6304
Authorizer Title
Dot Regulations Coordinator
Authorizer Email
N*********@o****.com
Narrative
Third party observed product vapors on pipeline right of way and called emergency number found on nearby pipeline right of way marker sign. Pipeline control center shutdown pipeline and dispatched company field personnel to release site. Company personnel verified release to be on oneok right of way at which time the segment of pipeline was isolated. Product in pipeline was displaced with nitrogen and a section of pipe was removed and replaced with new pipe. Inspection determined release was caused by microbiological corrosion.
Report Received Date 2010-11-18 00:00:00
Iyear 2010
Report Number 20100246
Supplemental Number 15612
Report Type Supplemental Final
Operator Id 32109 PHMSA Enforcement
Name Oneok Ngl Pipeline Lp
Operator Street Address 100 West Fifth Street
Operator City Name Tulsa
Operator State Abbreviation OK
Operator Postal Code 74103
Local Datetime 2010-11-01 14:55:00
Location Latitude 33.54657 Google Maps OpenStreetMap
Location Longitude -96.36906 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls 241
Intentional Release Bbls 0
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Notification From Public
Incident Identified Datetime 2010-11-01 14:55:00
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Shutdown Due Accident Ind Yes
Shutdown Datetime 2010-11-01 16:25:00
Restart Datetime 2010-11-06 09:30:00
On Site Datetime 2010-11-01 15:30:00
Nrc Rpt Datetime 2010-11-01 16:35:00
Nrc Rpt Num 958656 NRC Report How to search
Ignite Ind No
Explode Ind No
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Manual
Num Pub Evacuated 0
Pipe Fac Name Sterling 1 Index 10177
Segment Name Sterling 1 Between Valves S1-39 & S1-40
Onshore State Abbreviation Tx
Onshore Postal Code 75491
Onshore City Name Whitewright
Onshore County Name Fannin
Designated Location Milepost/valve Station
Designated Name 13265+65
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 54
Crossing No
Pipe Facility Type Interstate
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 8.625
Pipe Wall Thickness 0.188
Pipe Smys 46000
Pipe Specification 0.72
Pipe Seam Type Erw - High Frequency
Pipe Manufacturer Unknown
Pipe Coating Type Extruded Polyehylene
Installation Year 1981
Manufactured Year 1981
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 6358
Est Cost Prop Damage 244000
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 0
Prpty 250358
Accident Psig 1042
Mop Psig 1335
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Length Segment Isolated 84480
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind Yes
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind Yes
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details External Corrosion
Internal External External Corrosion
Visual Exam Results Localized Pitting
Microbiological Corrosion Ind Yes
Field Exam Basis Ind Yes
Other Basis Ind Yes
Corrosion Basis Details Visual Third Party Metallurgical Analysis Specialist
Underground Location Yes
Under Cathodic Protection Ind Yes
Cathodic Pro Start Year 1981
Shielding Evident Yes
Cathodic Survey Type Yes
Cp Annual Survey Ind Yes
Cp Annual Survey Year 2010
Prior Damage Yes
Collected Data Ind Yes
Other Recent Year 2007
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name P**** G**********
Preparer Email P****************@o****.com
Preparer Telephone 580-395-6238
Preparer Fax 580-395-2933
Prepared Date 2011-02-10 00:00:00
Authorizer Name N*** J****
Authorizer Telephone 580-395-6304
Authorizer Title Dot Regulations Coordinator
Authorizer Email N*********@o****.com
Narrative Third party observed product vapors on pipeline right of way and called emergency number found on nearby pipeline right of way marker sign. Pipeline control center shutdown pipeline and dispatched company field personnel to release site. Company personnel verified release to be on oneok right of way at which time the segment of pipeline was isolated. Product in pipeline was displaced with nitrogen and a section of pipe was removed and replaced with new pipe. Inspection determined release was caused by microbiological corrosion.

All rights reserved. Copyright © by ClearPHMSA