HL incident on 2010-01-21 — TX

Operator
Plantation Pipe Line Co
Cause
Natural Force Damage
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$85,000
Incident datetime
2010-01-21 12:30
Report number
Location
TX
Narrative
The pumping station is an unmanned facility. It appears that the 2-inch drain valve on the mdg 18-inch pipeline block valve was compromised during recent freezing weather. Product dripped from the drain valve into a concrete containment basin underneath the block valve. The product then flowed down a pvc drain line and into the facility's catchment basin. No product was released from the catchment basin. The drain to the containment basin was partially blocked with debris which caused water and gasoline to overflow during a significant rain event and the product was released onto the land surface in the immediate vicinity of the block valve. The product apparently migrated through the subsurface and along one of the facilities pipelines and was discharging into a shallow roadside ditch located immediately east of the facility where the pipelines exit the facility. Product was observed in the shallow ditch for a distance of approximately 300 feet south of where it was discharging into the ditch.
Detailed record list
Report Received Date
2010-08-16 00:00:00
Iyear
2010
Report Number
20100177
Supplemental Number
15873
Report Type
Supplemental Final
Operator Id
Name
Plantation Pipe Line Co
Operator Street Address
1001 Louisiana St Suite 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2010-01-21 12:30:00
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
6.76
Recovered Bbls
6.76
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Notification From Public
Incident Identified Datetime
2010-01-21 12:30:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2010-01-21 12:30:00
Restart Datetime
2010-01-21 20:35:00
On Site Datetime
2010-01-21 14:15:00
Nrc Rpt Datetime
2010-01-21 13:38:00
Nrc Rpt Num
Ignite Ind
No
Explode Ind
No
Upstream Valve Type Ind
Remotely Controlled
Downstream Valve Type Ind
Remotely Controlled
Pipe Fac Name
Fluker Station
Segment Name
Mdg 18b-4a
Onshore State Abbreviation
La
Onshore Postal Code
70441
Onshore City Name
Greensburg
Onshore County Name
St. Helena
Designated Location
Milepost/valve Station
Federal
No
Location Type
Originated On Operator-Controlled Property, But Then Flowed Or Migrated Off The Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Valve
Valve Type
Auxiliary Or Other Valve
Installation Year
2000
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
Yes
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
Yes
Surface Contam Ind
Yes
Amount Released
0.07
Rel Water Name
Drainage Swale On North S
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
570
Est Cost Prop Damage
85000
Est Cost Emergency
105000
Est Cost Environmental
10000
Est Cost Other
0
Prpty
200570
Accident Psig
900
Mop Psig
1480
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
70
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Natural Force Damage
Cause Details
Temperature
Natural Force Type
Temperature
Temperature Subtype
Frozen Components
Nf Extreme Weather Ind
No
Preparer Name
Q****** H* F******
Preparer Title
Manager - Compliance Codes And Standards
Preparer Email
Q**************@k***********.com
Preparer Telephone
(770) 751-4240
Preparer Fax
(770) 751 4130
Prepared Date
2011-06-21 00:00:00
Authorizer Name
Q****** H* F******
Authorizer Telephone
(770) 751-4240
Authorizer Title
Manager - Compliance Codes And Standards
Authorizer Email
Q**************@k***********.com
Narrative
The pumping station is an unmanned facility. It appears that the 2-inch drain valve on the mdg 18-inch pipeline block valve was compromised during recent freezing weather. Product dripped from the drain valve into a concrete containment basin underneath the block valve. The product then flowed down a pvc drain line and into the facility's catchment basin. No product was released from the catchment basin. The drain to the containment basin was partially blocked with debris which caused water and gasoline to overflow during a significant rain event and the product was released onto the land surface in the immediate vicinity of the block valve. The product apparently migrated through the subsurface and along one of the facilities pipelines and was discharging into a shallow roadside ditch located immediately east of the facility where the pipelines exit the facility. Product was observed in the shallow ditch for a distance of approximately 300 feet south of where it was discharging into the ditch.
Report Received Date 2010-08-16 00:00:00
Iyear 2010
Report Number 20100177
Supplemental Number 15873
Report Type Supplemental Final
Operator Id 15674 PHMSA Enforcement
Name Plantation Pipe Line Co
Operator Street Address 1001 Louisiana St Suite 1000
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2010-01-21 12:30:00
Location Latitude 30.78251 Google Maps OpenStreetMap
Location Longitude -90.75851 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Gasoline (Non-Ethanol)
Unintentional Release Bbls 6.76
Recovered Bbls 6.76
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Notification From Public
Incident Identified Datetime 2010-01-21 12:30:00
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Shutdown Due Accident Ind Yes
Shutdown Datetime 2010-01-21 12:30:00
Restart Datetime 2010-01-21 20:35:00
On Site Datetime 2010-01-21 14:15:00
Nrc Rpt Datetime 2010-01-21 13:38:00
Nrc Rpt Num 929258 NRC Report How to search
Ignite Ind No
Explode Ind No
Upstream Valve Type Ind Remotely Controlled
Downstream Valve Type Ind Remotely Controlled
Pipe Fac Name Fluker Station
Segment Name Mdg 18b-4a
Onshore State Abbreviation La
Onshore Postal Code 70441
Onshore City Name Greensburg
Onshore County Name St. Helena
Designated Location Milepost/valve Station
Federal No
Location Type Originated On Operator-Controlled Property, But Then Flowed Or Migrated Off The Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Valve
Valve Type Auxiliary Or Other Valve
Installation Year 2000
Material Involved Carbon Steel
Release Type Leak
Leak Type Seal Or Packing
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment Yes
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind Yes
Surface Contam Ind Yes
Amount Released 0.07
Rel Water Name Drainage Swale On North S
Could Be Hca Yes
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 570
Est Cost Prop Damage 85000
Est Cost Emergency 105000
Est Cost Environmental 10000
Est Cost Other 0
Prpty 200570
Accident Psig 900
Mop Psig 1480
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Length Segment Isolated 70
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Natural Force Damage
Cause Details Temperature
Natural Force Type Temperature
Temperature Subtype Frozen Components
Nf Extreme Weather Ind No
Preparer Name Q****** H* F******
Preparer Title Manager - Compliance Codes And Standards
Preparer Email Q**************@k***********.com
Preparer Telephone (770) 751-4240
Preparer Fax (770) 751 4130
Prepared Date 2011-06-21 00:00:00
Authorizer Name Q****** H* F******
Authorizer Telephone (770) 751-4240
Authorizer Title Manager - Compliance Codes And Standards
Authorizer Email Q**************@k***********.com
Narrative The pumping station is an unmanned facility. It appears that the 2-inch drain valve on the mdg 18-inch pipeline block valve was compromised during recent freezing weather. Product dripped from the drain valve into a concrete containment basin underneath the block valve. The product then flowed down a pvc drain line and into the facility's catchment basin. No product was released from the catchment basin. The drain to the containment basin was partially blocked with debris which caused water and gasoline to overflow during a significant rain event and the product was released onto the land surface in the immediate vicinity of the block valve. The product apparently migrated through the subsurface and along one of the facilities pipelines and was discharging into a shallow roadside ditch located immediately east of the facility where the pipelines exit the facility. Product was observed in the shallow ditch for a distance of approximately 300 feet south of where it was discharging into the ditch.

All rights reserved. Copyright © by ClearPHMSA