Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2010-10-20 — AL
Operator
Scottsboro Water Sewer & Gas Board
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$1,586
Incident datetime
2010-10-20 19:37
Report number
Location
AL
Narrative
This incident occured at a privately owned service station/convenience store on october 20,2010.The natural gas meter set was located in the back corner of the parking lot approximately five feet from side of service station next to a utility pole. A privately owned vehicle traveled off the public roadway across the service station parking lot.The vehicle struck the natural gas meter set breaking the 3/4 inch nipple between the natural gas service line riser valve (stop cock) and the gas pressure regulator. Natural gas release occured at this time. Natural gas ignited ( ignition source unknown). Burning vehicle and burning natural gas ignited the wood siding and roof on the service station/convenience store,as well as,the utility pole. Police and fire personnel were the first to arrive at the scene. Police requested assistance from gas system personnel who immediately reported to the scene and closed the valve on the natural gas main line stopping the flow of gas to the service line and broken meter set. Fireman extingushed the fire on the burning vehicle and convenience store. Gas system personnel isolated the natural gas service line for the service station/convenience store from the rest of the natural gas system and restored service to twelve residences in the area the same night. Gas system personnel restored the service line/meter set for the convenience store on november 3, 2010. No one was killed or injured. No one was hospitalized. The estimated damage to the driver's vehicle was $4000. The estimated damage to the service station/convenience store was approximately $250,000. Police arrested the driver of the vehicle for driving under the influence and obstructing governmental operations.
Detailed record list
Occurred At
2010-10-20 19:37:00
Year
2010
Report Received Date
2010-11-08 00:00:00
Iyear
2010.0
Report Number
20100101.0
Supplemental Number
15134.0
Report Type
Original Final
Operator Id
18140
Name
Scottsboro Water Sewer & Gas Board
Operator Street Address
P O Box 550
Operator City Name
Scottsboro
Operator State Abbreviation
AL
Operator Postal Code
35768
Local Datetime
2010-10-20 19:34:00
Location Street Address
4623 South Broad Street
Location City Name
Scottsboro
Location State Abbreviation
AL
Location Postal Code
35769
Location Latitude
34.6118
Location Longitude
-86.06668
Nrc Rpt Datetime
2010-10-21 14:00:00
Nrc Rpt Num
957657
Commodity Released Type
Natural Gas
Unintentional Release
8.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
4.0
Incident Identified Datetime
2010-10-20 19:37:00
On Site Datetime
2010-10-20 19:45:00
Federal
No
Location Type
Private Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing
No
Pipe Facility Type
Municipally Owned
System Part Involved
Outside Meter/regulator Set
Installation Year
1985.0
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Wt Steel
0.113
Release Type
Other
Release Type Details
3/4 " Nipple Was Broke In Threaded Joint Due To Car Impact.
Class Location Type
Class 2 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
1586.0
Est Cost Emergency
1097.0
Est Cost Other
0.0
Est Cost Unintentional Release
100.0
Prpty
2783.0
Commercial Affected
1.0
Industrial Affected
0.0
Residences Affected
12.0
Accident Psig
168.0
Normal Psig
175.0
Mop Psig
200.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Outside Force Type
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Vehicle Subtype
Third Party
Preparer Name
P*** D* B*****
Preparer Title
Gas Superintendent
Preparer Email
P***@s*********.org
Preparer Telephone
256-574-1744
Preparer Fax
256-574-1965
Authorizer Name
R** E* L****
Authorizer Title
General Manager
Authorizer Telephone
256-574-1744
Authorizer Email
R**@s*********.org
Narrative
This incident occured at a privately owned service station/convenience store on october 20,2010.The natural gas meter set was located in the back corner of the parking lot approximately five feet from side of service station next to a utility pole. A privately owned vehicle traveled off the public roadway across the service station parking lot.The vehicle struck the natural gas meter set breaking the 3/4 inch nipple between the natural gas service line riser valve (stop cock) and the gas pressure regulator. Natural gas release occured at this time. Natural gas ignited ( ignition source unknown). Burning vehicle and burning natural gas ignited the wood siding and roof on the service station/convenience store,as well as,the utility pole. Police and fire personnel were the first to arrive at the scene. Police requested assistance from gas system personnel who immediately reported to the scene and closed the valve on the natural gas main line stopping the flow of gas to the service line and broken meter set. Fireman extingushed the fire on the burning vehicle and convenience store. Gas system personnel isolated the natural gas service line for the service station/convenience store from the rest of the natural gas system and restored service to twelve residences in the area the same night. Gas system personnel restored the service line/meter set for the convenience store on november 3, 2010. No one was killed or injured. No one was hospitalized. The estimated damage to the driver's vehicle was $4000. The estimated damage to the service station/convenience store was approximately $250,000. Police arrested the driver of the vehicle for driving under the influence and obstructing governmental operations.
| Occurred At | 2010-10-20 19:37:00 |
|---|---|
| Year | 2010 |
| Report Received Date | 2010-11-08 00:00:00 |
| Iyear | 2010.0 |
| Report Number | 20100101.0 |
| Supplemental Number | 15134.0 |
| Report Type | Original Final |
| Operator Id | 18140 PHMSA Enforcement |
| Name | Scottsboro Water Sewer & Gas Board |
| Operator Street Address | P O Box 550 |
| Operator City Name | Scottsboro |
| Operator State Abbreviation | AL |
| Operator Postal Code | 35768 |
| Local Datetime | 2010-10-20 19:34:00 |
| Location Street Address | 4623 South Broad Street |
| Location City Name | Scottsboro |
| Location State Abbreviation | AL |
| Location Postal Code | 35769 |
| Location Latitude | 34.6118 Google Maps OpenStreetMap |
| Location Longitude | -86.06668 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2010-10-21 14:00:00 |
| Nrc Rpt Num | 957657 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 8.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Explode Ind | No |
| Num Pub Evacuated | 4.0 |
| Incident Identified Datetime | 2010-10-20 19:37:00 |
| On Site Datetime | 2010-10-20 19:45:00 |
| Federal | No |
| Location Type | Private Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set) |
| Crossing | No |
| Pipe Facility Type | Municipally Owned |
| System Part Involved | Outside Meter/regulator Set |
| Installation Year | 1985.0 |
| Material Involved | Steel |
| Steel Seam Type | Other |
| Steel Seam Type Details | Unknown |
| Wt Steel | 0.113 |
| Release Type | Other |
| Release Type Details | 3/4 " Nipple Was Broke In Threaded Joint Due To Car Impact. |
| Class Location Type | Class 2 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 1586.0 |
| Est Cost Emergency | 1097.0 |
| Est Cost Other | 0.0 |
| Est Cost Unintentional Release | 100.0 |
| Prpty | 2783.0 |
| Commercial Affected | 1.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 12.0 |
| Accident Psig | 168.0 |
| Normal Psig | 175.0 |
| Mop Psig | 200.0 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Emergency Responder |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Other Outside Force Damage |
| Cause Details | Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation |
| Outside Force Type | Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation |
| Vehicle Subtype | Third Party |
| Preparer Name | P*** D* B***** |
| Preparer Title | Gas Superintendent |
| Preparer Email | P***@s*********.org |
| Preparer Telephone | 256-574-1744 |
| Preparer Fax | 256-574-1965 |
| Authorizer Name | R** E* L**** |
| Authorizer Title | General Manager |
| Authorizer Telephone | 256-574-1744 |
| Authorizer Email | R**@s*********.org |
| Narrative | This incident occured at a privately owned service station/convenience store on october 20,2010.The natural gas meter set was located in the back corner of the parking lot approximately five feet from side of service station next to a utility pole. A privately owned vehicle traveled off the public roadway across the service station parking lot.The vehicle struck the natural gas meter set breaking the 3/4 inch nipple between the natural gas service line riser valve (stop cock) and the gas pressure regulator. Natural gas release occured at this time. Natural gas ignited ( ignition source unknown). Burning vehicle and burning natural gas ignited the wood siding and roof on the service station/convenience store,as well as,the utility pole. Police and fire personnel were the first to arrive at the scene. Police requested assistance from gas system personnel who immediately reported to the scene and closed the valve on the natural gas main line stopping the flow of gas to the service line and broken meter set. Fireman extingushed the fire on the burning vehicle and convenience store. Gas system personnel isolated the natural gas service line for the service station/convenience store from the rest of the natural gas system and restored service to twelve residences in the area the same night. Gas system personnel restored the service line/meter set for the convenience store on november 3, 2010. No one was killed or injured. No one was hospitalized. The estimated damage to the driver's vehicle was $4000. The estimated damage to the service station/convenience store was approximately $250,000. Police arrested the driver of the vehicle for driving under the influence and obstructing governmental operations. |